2006-08-04 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN DETAIN ON THEM AND ARE DIFFICULT TO
 READ. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 2) SHOW A/C EQUIPMENT LISTING WITH ALL
 THE PERTINENT INFORMATION ON THE
 MECHANICAL PLANS.
  
 3) THE MECHINACLE PLANS NEED THE
 ENGINEER"S SEAL ON THEM DUE TO HIS NAME
 AND INFORMATION IS IN THE TITLE BLOCK,
 PER FAC 61G15-23.002 .
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2
  
 5) ENERGY CALCULATIONS NEED THE ADDRESS,
 AND JURISDICTION NUMBER ON THEM.
  
 6) NEED TWO COPY'S OF ENERGY CAL'S FOR
 THE GUEST SUITE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  