Plan Review Notes
Plan Review Notes For Permit 06071373
Permit Number 06071373
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-26 00:00:00*******UNSAT ************
  
 1) NOTE: PLEASE SEE MISSING RECEPT FOR
 WHAT APPEARS TO BE MORE THAN 2 FT OF
 WALL IN MAIN HOUSE.
  
 2) NOTE: PLEASE COMPLETE PANEL SCHEDULES
 TO INDICATE ALL SPECIFYOED AREAS AND
 RMS. IE; LIV RM TLS, DINING RECEPTS ,
 BEDRM #1 RECEPTS ETC.
 408.4,240.4,310.16
  
 3) NOTE: PLEASE SEE PANEL FOR MAIN HOUSE
 IS NOT ON PLANS., 110.26,240.24 ETC
 PLEASE ALSO SHOW SERVICE AND LOCATION OF
 SERVICE. PLEASE SEE NOTES FOR GUEST
 HOUSE ALSO AS MAINS DO NOT APPEAR TO BE
 GROUPED ETC.
 PLEASE SEE 230.70,230.72,225.31-225.39
 PLEASE SEE MISSING DISCONNECTING MEANS
 AT GUEST HOUSE. RISER SHOWS A DISCONNECT
 HOWEVER IT IS NOT SHOWN ON PLANS WHERE
 THIS ITS.
  
 4) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT GUEST HOUSE PER
 250.32, 250.50
  
 5) NOTE: PLEASE CORRELATE PLANS AS GUEST
 HOUSE SHOWS 60A PANEL, AND RISER SHOWS
 100A ALONG WITH PANEL SCHEDULE.
 PLEASE SEE LOAD SHOWN EXCEEDS THE RATING
 OF THE 60A PANEL.
 2404.310.16
 106.1.2 FBC
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 7) NOTE: PLEASE VERIFY THE 60A OCP SHOWN
 FO THE 7.5KW HEAT IN GUEST HOUSE.
  
 8) NOTE: PLEASE SEE DINING RM SHALL BE
 ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE IF DINING IS ON
 THEIR OWN, PLEASE SEE 210.52B1,210.11C1
 AND 220.16 AS THE THESE SHALL BE FIGURED
 AS 1500 VA.
  
 9) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR
 SD'S LOCATED WITHIN 20' OF COOKING
 EQUIPMENT.
  
 10) NOTE: PLEASE CLARIFY IF THEIR ARE
 GONG TO BE LAUNDRY FACILITIES IN GUEST
 HOUSE.?
  
 ** PLEASE SEE ANY POSSIBLE ZONING
 COMMENTS WHICH MAY AFFECT PLANS.
  
 ** BEFORE AND WHEN RESUBMITTING PLANS,
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 SUBMIT ONE COPY OF THE OLD/VOIDED SHEETS
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  