| 2006-07-26 00:00:00 | *******UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE MISSING RECEPT FOR |
| | WHAT APPEARS TO BE MORE THAN 2 FT OF |
| | WALL IN MAIN HOUSE. |
| | |
| | 2) NOTE: PLEASE COMPLETE PANEL SCHEDULES |
| | TO INDICATE ALL SPECIFYOED AREAS AND |
| | RMS. IE; LIV RM TLS, DINING RECEPTS , |
| | BEDRM #1 RECEPTS ETC. |
| | 408.4,240.4,310.16 |
| | |
| | 3) NOTE: PLEASE SEE PANEL FOR MAIN HOUSE |
| | IS NOT ON PLANS., 110.26,240.24 ETC |
| | PLEASE ALSO SHOW SERVICE AND LOCATION OF |
| | SERVICE. PLEASE SEE NOTES FOR GUEST |
| | HOUSE ALSO AS MAINS DO NOT APPEAR TO BE |
| | GROUPED ETC. |
| | PLEASE SEE 230.70,230.72,225.31-225.39 |
| | PLEASE SEE MISSING DISCONNECTING MEANS |
| | AT GUEST HOUSE. RISER SHOWS A DISCONNECT |
| | HOWEVER IT IS NOT SHOWN ON PLANS WHERE |
| | THIS ITS. |
| | |
| | 4) NOTE: PLEASE SEE MISSING GROUNDING |
| | ELECTRODE SYSTEM AT GUEST HOUSE PER |
| | 250.32, 250.50 |
| | |
| | 5) NOTE: PLEASE CORRELATE PLANS AS GUEST |
| | HOUSE SHOWS 60A PANEL, AND RISER SHOWS |
| | 100A ALONG WITH PANEL SCHEDULE. |
| | PLEASE SEE LOAD SHOWN EXCEEDS THE RATING |
| | OF THE 60A PANEL. |
| | 2404.310.16 |
| | 106.1.2 FBC |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 7) NOTE: PLEASE VERIFY THE 60A OCP SHOWN |
| | FO THE 7.5KW HEAT IN GUEST HOUSE. |
| | |
| | 8) NOTE: PLEASE SEE DINING RM SHALL BE |
| | ON ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS. PLEASE SEE IF DINING IS ON |
| | THEIR OWN, PLEASE SEE 210.52B1,210.11C1 |
| | AND 220.16 AS THE THESE SHALL BE FIGURED |
| | AS 1500 VA. |
| | |
| | 9) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR |
| | SD'S LOCATED WITHIN 20' OF COOKING |
| | EQUIPMENT. |
| | |
| | 10) NOTE: PLEASE CLARIFY IF THEIR ARE |
| | GONG TO BE LAUNDRY FACILITIES IN GUEST |
| | HOUSE.? |
| | |
| | ** PLEASE SEE ANY POSSIBLE ZONING |
| | COMMENTS WHICH MAY AFFECT PLANS. |
| | |
| | ** BEFORE AND WHEN RESUBMITTING PLANS, |
| | PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | SUBMIT ONE COPY OF THE OLD/VOIDED SHEETS |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |