Plan Review Notes
Plan Review Notes For Permit 06071370
Permit Number 06071370
Review Stop M
Sequence Number 3
Notes
Date Text
2007-01-31 16:12:22*** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 10-24-07 NOTE #2, MECHANICAL
 PLANS FOR MAIN HOUSE AND COTTAGE, NEED JOB ADDRESS ON
 THEM.
  
 2) AS NOTED IN LAST REVIEW 10-24-07 NOTE #3, THE A/C
 SYSTEM FOR THE MAIN HOUSE IS OVER-SIZED, THE MAIN HOUSE
 MANUAL J CALCULATIONS ARE CALLING FOR 19,783 SENSIBLE
 BTU'S, THE MECHANICAL PLANS ARE CALLING FOR 33,322
 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL FOR 20% MORE
 THAN THE MANUAL J CAL'S, PER 2004 FBC 13-607.1.ABC.1.1,
 PLEASE CORRECT.
  
 3) AS NOTED IN LAST REVIEW 10-24-07 NOTE #4. SEE MAIN
 HOUSE MECH. PLAN, 12"RETURN AIR TRANSFER DUCT TO
 MASTER SUITE IS TO SMALL. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS,
 EXECPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED. PER 2004 FBC/R M1602.4.
  
 4) PLEASE SHOW ON MECHANICAL PLANS WERE THE CLOTHES
 DRYER VENT WILL TERMINATE (VENT MAY NOT DISCHARGE NEAR
 A/C CONDENSER UNIT).
  
 5) SEE MECHANICAL PLANS TO MAIN HOUSE, WHITE-OUT MAY
 NOT BE USED ON PLANS, AND DO NOT SUBMIT CHANGES IN PEN.
 PLEASE MAKE COPY'S AFTER CHANGES HAVE BEEN MADE AND
 SUBMIT COPY'S.
  
 6) SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.