Plan Review Notes
Plan Review Notes For Permit 06071370
Permit Number 06071370
Review Stop M
Sequence Number 2
Notes
Date Text
2006-10-24 13:41:13*** DENIED ***
 1) MECHANICAL PLANS NEED THE NAME AND SIGNATURE OF THE
 DESIGN PERSON ON THEM, FOR MAIN HOUSE AND COTTAGE. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 2) SEE MECHANICAL PLANS FOR MAIN HOUSE AND COTTAGE,
 NEED JOB ADDRESS ON THEM.
  
 3) THE MAIN HOUSE MANUAL J CALCULATIONS ARE CALLING FOR
 14,200 TOTAL SENSIBLE BTU'S, THE MECH. PLANS ARE
 CALLING FOR 33,322 TOTAL SENSIBLE BTU'S, THE PLANS CAN
 ONLY CALL FOR 20% MORE THAN THE MANUAL J CAL'S, PRE
 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 4) SEE MAIN HOUSE MECH. PLAN, 10"RETURN AIR TRANSFER
 DUCT TO MASTER SUITE IS TO SMALL, PLEASE CORRECT, SEE
 NOTE #5.
  
 5)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.