| Date |
Text |
| 2006-10-24 13:41:13 | *** DENIED *** |
| | 1) MECHANICAL PLANS NEED THE NAME AND SIGNATURE OF THE |
| | DESIGN PERSON ON THEM, FOR MAIN HOUSE AND COTTAGE. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE |
| | FOR THE DESIGN. PER FBC 104.2.1 . |
| | |
| | 2) SEE MECHANICAL PLANS FOR MAIN HOUSE AND COTTAGE, |
| | NEED JOB ADDRESS ON THEM. |
| | |
| | 3) THE MAIN HOUSE MANUAL J CALCULATIONS ARE CALLING FOR |
| | 14,200 TOTAL SENSIBLE BTU'S, THE MECH. PLANS ARE |
| | CALLING FOR 33,322 TOTAL SENSIBLE BTU'S, THE PLANS CAN |
| | ONLY CALL FOR 20% MORE THAN THE MANUAL J CAL'S, PRE |
| | 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT. |
| | |
| | 4) SEE MAIN HOUSE MECH. PLAN, 10"RETURN AIR TRANSFER |
| | DUCT TO MASTER SUITE IS TO SMALL, PLEASE CORRECT, SEE |
| | NOTE #5. |
| | |
| | 5)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |