| Plan Review Notes For Permit 06071370 |
| Permit Number |
06071370 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-26 00:00:00 | DENIED; | | | 1.PLEASE INCLUDE GUEST HOUSE ON THE | | | PLUMBING SANITARY RISER DIAGRAM. | | | 2.IS WATER SERVICE TO BOTH BUILDINGS | | | FROM THE SAME METER IF SO A BACKFLOW | | | PREVENTER IS REQUIRED TO BE INSTALLED AT | | | THE WATER METER BY THE UTILITY | | | DEPARTMENT. | | | 3.IS WATER HEATER IN MAIN HOUSE THE HOT | | | WATER SUPPLY FOR THE BACK HOUSE? IF SO | | | PLEASE SHOW ON THE PLANS THE DISTANCE | | | FROM THE W/H TO THE LAST FIXTURE. IF | | | 100' A METHOD OF MAINTAINING THE | | | TEMPERATURE IN ACCORDANC WITH CHAPTER 13 | | | OF THE FBC-2004 BUILDING CODE MUST BE | | | INSTALLED. | | | 4.IF A BACKFLOW IS REQUIRED THEN A MEANS | | | OF THERMAL EXPANSION SHELL BE REQUIRED. | | | SEE SECTION 607.3. SHOW ON DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|