| 2006-08-07 00:00:00 | *** DENIED *** |
| | 1) MECHANICAL PLANS HAVE TO MUCH FLOOR |
| | PLAN DETAIL ON THEM AND ARE DIFFICULT TO |
| | READ. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY. PER 2004 FBC 106.1.1 |
| | . |
| | |
| | 2) THE MECHANICAL PLANS NEED TO BE |
| | SEALED BY THE ENGINEER AS HIS NAME AND |
| | INFORMATION IS IN THE TITLE BLOCK, PER |
| | FAC 61G15-23.002 (LOOK UP PLAGIARISM). |
| | |
| | 3) ONE COPY OF THE ENERGY CALCULATIONS |
| | WERE SIGNED IN PENCIL BY THE PREPARER, |
| | DOCUMENTS MUST BE SIGNED IN PEN. AND |
| | SUBMIT TWO COPYS OF THE E-CAL'S FOR THE |
| | GUEST HOUSE. |
| | |
| | 4) ENERGY CALCULATIONS NEED TO BE SIGNED |
| | BY OWNER/AGENT ALSO, PER 2004 FBC |
| | 13-600.3.ABC.2 . |
| | |
| | 5) SHOW A EQUIPMENT LISTING WITH ALL |
| | PERTINENT INFORMATION ON THE MECHANICAL |
| | PLANS. |
| | |
| | 6) SHOW CFM'S AT EACH SUPPLY AIR GRILL. |
| | |
| | 7) SHOW LOCATION OF CLOTHES DRYER VENT TERMINATION, ON |
| | MECHANICAL PLANS. |
| | |
| | 8) ALL RETURN AIR TRANSFER DUCTS ARE TO |
| | SMALL, SEE NOTE #9. |
| | |
| | 9) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |