| Plan Review Notes For Permit 06071369 |
| Permit Number |
06071369 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-01 00:00:00 | | | | | | | DENIED | | | | | | 1) PLEASE MARK MIAMI-DADE NOA DRAWING | | | WITH THE MOUNTING METHOD, ANCHOR TYPE, | | | CONST TYPE (WOOD, CONCRETE, ETC) | | | | | | 2) PROVIDE THE MEAN ROOF HEIGHT ALONG | | | WITH THE SHUTTER SPANS IN ORDER TO | | | DETERMINE THE PRESSURES ON THE PROVIDED | | | ENGINEERING | | | | | | 3) MIAMI-DADE NOA 02-0404.01 HAS BEEN | | | REVISED NEW NOA 05-1220.12 SHOULD BE | | | SUBMITTED | | | | | | 4) THE PRESSURE THAT WAS INDICATED ON | | | THE DRAWING FOR ANCHOR SPACING CANNOT BE | | | USED FOR SHUTTER BECAUSE THAT WOULD | | | LIMIT THE SPAN TO 6'-0" OR LESS. PLEASE | | | USE THE DESIGN PRESSURE THAT IS REQUIRED | | | BY THE SUBMITTED ENGINEERING | | | | | | 5) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|