| Date |
Text |
| 2007-09-20 10:30:08 | |
| | ** DENIED 4TH TIME ** |
| | |
| | THIS IS THE FIRST REVIEW UNDER NEW PLANS FROM A NEW |
| | DESIGN PROFESSIONAL(S). |
| | |
| | ** PLEASE SEE THERE ARE NEW NOTES BASED ON THE PLANS |
| | BEING SUBMITTED FOR THE FIRST TIME. THESE PLANS WERE |
| | NOT PREVIOUSLY SUBMITTED FOR REVIEW. |
| | |
| | 1) NOTE: PLEASE KNOW THIS PROJECT WAS APPLIED FOR |
| | PERMIT UNDER THE PREVIOUS ADOPTED CODE CYCLE IN THE |
| | FLORIDA STATUTES 553.73. |
| | PLEASE SEE THIS IS UNDER THE 2002 NFPA-70 AS THIS WAS |
| | APPLIED FOR PERMIT BEFORE DECCEMBER 8TH, 2006. PLEASE |
| | ADJUST PLANS. |
| | |
| | 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS FOR LAYOUT OF |
| | DWELLING DOES NOT CONTAIN ANY DESIGN PROFESSIONAL FOR |
| | TAKING RESPONSIBILITY OF PLANS. |
| | PLEASE SEE THE SHEET WHICH CONTAINS THE ELECTRICAL |
| | PANEL SCHEDULE AND RISER CONTAINS AN ENGINEER SIGNED, |
| | DATED AND SEALED ALONG WITH TITLE BLOCKS. |
| | ** PLEASE KNOW A DESIGN PROFESSIONAL MUST TAKE |
| | RESPONSIBILITY OF SAID PLANS. FS 471, 481, 489, ETC FBC |
| | ADMIN SECTION, 106.1.2, 106.3.1, 110.1.2 ETC. |
| | |
| | 3) NOTE: PLEASE SHOW DISCONNECTS FOR THE CONDENSING |
| | UNITS PER 440.11, 110.26. |
| | |
| | 4) NOTE: PLEASE SEE THE A/C SYSTEMS WHICH ARE SHOWN ON |
| | PLANS DO NOT CORRELATE WITH THE LOAD CALCULATIONS, OVER |
| | CURRENT PROTECTION AND LOCATIONS. |
| | PLEASE SEE THE MISSING AIR HANDLER UNIT FOR 2ND FLOOR |
| | W/ DISCONNECT. 440.11, 110.26 |
| | PLEASE SEE THE LOADS SHOWN ON CALCULATIONS EXCEED THAT |
| | OF THE RATING OF THE BRANCH CIRCUITS FEEDING EACH OF |
| | THESE SYSTEMS. PLEASE SEE 220.19, 240.4, 310.16, |
| | 424.3B |
| | PLEASE SEE THE OVER CURRENT PROTECTION IS TO MEET THE |
| | MINIMUM FOR HEAT LOADS PER 424.3B (125% WHICH IS FOR |
| | OVER CURRENT PROTECTION). |
| | PLEASE ADJUST THE OCP, CONDUCTOR SIZES, LOCATIONS AND |
| | LOADS AS NEEDED. |
| | |
| | 5) NOTE: PLEASE SEE THE LOAD, OVER CURRENT PROTECTION |
| | AND SIZE OF FEEDERS TO PANEL *B* DO NOT MEET THE |
| | REQUIREMENTS FOR THE LOADS. |
| | PLEASE ADJUST. |
| | 240.4, 310.16, 408.4 |
| | |
| | 6) NOTE: PLEASE SHOW THE LOCATION OF PANEL *B*. 110.26, |
| | 408.7, 240.24D |
| | |
| | 7) NOTE: PLEASE CORRELATE CIRCUITING ON PLANS. PLEASE |
| | SEE THERE ARE SEVERAL CIRCUITS ON PANEL SCHEDULE(S) |
| | WHICH ARE NOT THE SAME AS ON PLANS. |
| | PLEASE SEE FOR EXAMPLE: |
| | B-7 ON PLANS IS FOR REFRIGERATOR, YET THE PANEL |
| | SCHEDULE SHOWS THIS AS THE DISHWASHER. |
| | B-9 NOT ON PANEL SCHEDULE YET SHOWN AS DISHWASHER ON |
| | PLANS. |
| | PLEASE SEE THERE ARE SOME OTHERS PLEASE BE SURE TO |
| | VERIFY ALL. |
| | |
| | 8) NOTE: PLEASE SEE MISSING DISPOSAL ON PLANS. PLEASE |
| | BE SURE TO SEE 210.4B FOR REQUIRED 2-POLE BREAKER IF |
| | THE DISHWASHER AND DISPOSAL IS ON THE SAME YOKE. |
| | 408.4. |
| | FBC 106.3.5.4 |
| | |
| | 9) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR |
| | REQUIRED CIRCUITING FOR DINING ROOM/AREA RECEPTACLE |
| | CIRCUITS. PLEASE SEE THE AREAS AS SPECIFIED IN 210.52B1 |
| | ARE TO BE ON ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS. PLEASE ALSO SEE THAT THE LOAD SHALL BE |
| | FIGURED ON EACH OF THOSE CIRCUITS AT A MINIMUM OF |
| | 1500VA FOR EACH. THIS INCLUDES ANY ABOVE THE MINIMUM |
| | FOR THE KITCHEN SMALL APPLIANCE CIRCUITS. |
| | PLEASE SEE AS NOTED IN SECTIONS, THESE MUST BE 20AMP |
| | AND #12 AWG. |
| | PLEASE ADJUST PLANS FOR THESE. (EXAMPLE CIRCUIT #33). |
| | |
| | 10) NOTE: PLEASE SEE THERE ARE SEVERAL BATHROOM |
| | CIRCUITS WHICH DO NOT MEET 210.52D, 210.11C3. PLEASE |
| | SEE ONE CIRCUIT WHICH IS #22 MENTIONS THIS IS ALSO TO |
| | FEED HALL, WHICH IS NOT PERMITTED. |
| | PLEASE SEE THESE ARE SHOWN WITH THE REQUIRED #12 |
| | HOWEVER NOT THE REQUIRED 20AMP BREAKER. |
| | PLEASE ADJUST ALL ON PLANS/PANEL SCHEDULES AS NEEDED. |
| | (19,22,37,38,39 ETC) |
| | |
| | 11) NOTE: PLEASE SEE 210.12 FOR SMOKE ALARM CIRCUIT |
| | WHICH IS NOT SHOWN AS ARC FAULT PROTECTED AS REQUIRED. |
| | ALL OUTLETS ARE TO BE AFCI. PLEASE ADJUST AND LIST ON |
| | PANEL SCHEDULE. |
| | |
| | 12) NOTE: PLEASE INDICATE THE AIC RATING FOR |
| | MAINS/PANELS/BREAKERS PER 110.9. |
| | FBC 106.1.2, 106.1.3, 106.3.5.4 |
| | |
| | 13) NOTE: PLEASE CLARIFY *UTILITY ROOM* CIRCUITS WHICH |
| | ARE SHOWN AS #12, 15AMP, AND GFI? |
| | THESE CIRCUITS 17 AND 23 ARE FEEDING OTHER AREAS ALSO. |
| | |
| | 14) NOTE: PLEASE SEE WATER HEATER IS BEING SHOWN ON |
| | CIRCUITS 5/9 ON PLAN WHICH IS NOT POSSIBLE FOR |
| | 220/240V. PLEASE SEE THE PANEL SCHEDULE AS THIS CALLS |
| | FOR 5/7. |
| | PLEASE ALSO SEE THE SYMBOL SHOWN FOR CONNECTION OF THE |
| | WATER HEATER LENDS THIS AS BEING PLUG IN CONNECTION. |
| | PLEASE SEE 422.30, 422.31 AS THIS UNIT IS REQUIRED TO |
| | BE HARDWIRED AND MAY NOT PLUG-IN. |
| | A DISCONNECT IS NOT REQUIRED WHEN THE PANEL IS WITHIN |
| | SIGHT, HOWEVER MAY BE INSTALLED. |
| | |
| | 15) NOTE: PLEASE VERIFY IF THE CONDUIT FROM THE METER |
| | TO THE PANEL INSIDE IS UNDERGROUND/SLAB OR NOT. PLEASE |
| | SEE 230.70,230.71, AS A MAIN DISCONNECT WITH OVER |
| | CURRENT PROTECTION WOULD BE REQUIRED OUTSIDE IF MORE |
| | THAN 8FT OF UNPROTECTED CONDUCTORS ARE INSIDE THE |
| | DWELLING. |
| | |
| | 16) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE ONLY: |
| | THE LOW VOLTAGE AS SHOWN ON PLANS WILL BE REQUIRED TO |
| | BE UNDER A SEPARATE PERMIT. |
| | PLEASE KNOW THESE PLANS MAY BE USED FOR REFERENCING AND |
| | A *TURN AROUND* PERMIT WILL BE ISSUED. |
| | ** THIS IS ONLY NOTED FOR INFORMATION TO THE OWNER. |
| | |
| | 17) NOTE: |
| | |
| | |
| | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| | THIS REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-20 09:04:36 | NEW PLANS SUBMITTED ON 9/13/07 |