Plan Review Notes
Plan Review Notes For Permit 06071334
Permit Number 06071334
Review Stop E
Sequence Number 5
Notes
Date Text
2007-09-20 10:30:08 
 ** DENIED 4TH TIME **
  
 THIS IS THE FIRST REVIEW UNDER NEW PLANS FROM A NEW
 DESIGN PROFESSIONAL(S).
  
 ** PLEASE SEE THERE ARE NEW NOTES BASED ON THE PLANS
 BEING SUBMITTED FOR THE FIRST TIME. THESE PLANS WERE
 NOT PREVIOUSLY SUBMITTED FOR REVIEW.
  
 1) NOTE: PLEASE KNOW THIS PROJECT WAS APPLIED FOR
 PERMIT UNDER THE PREVIOUS ADOPTED CODE CYCLE IN THE
 FLORIDA STATUTES 553.73.
 PLEASE SEE THIS IS UNDER THE 2002 NFPA-70 AS THIS WAS
 APPLIED FOR PERMIT BEFORE DECCEMBER 8TH, 2006. PLEASE
 ADJUST PLANS.
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS FOR LAYOUT OF
 DWELLING DOES NOT CONTAIN ANY DESIGN PROFESSIONAL FOR
 TAKING RESPONSIBILITY OF PLANS.
 PLEASE SEE THE SHEET WHICH CONTAINS THE ELECTRICAL
 PANEL SCHEDULE AND RISER CONTAINS AN ENGINEER SIGNED,
 DATED AND SEALED ALONG WITH TITLE BLOCKS.
 ** PLEASE KNOW A DESIGN PROFESSIONAL MUST TAKE
 RESPONSIBILITY OF SAID PLANS. FS 471, 481, 489, ETC FBC
 ADMIN SECTION, 106.1.2, 106.3.1, 110.1.2 ETC.
  
 3) NOTE: PLEASE SHOW DISCONNECTS FOR THE CONDENSING
 UNITS PER 440.11, 110.26.
  
 4) NOTE: PLEASE SEE THE A/C SYSTEMS WHICH ARE SHOWN ON
 PLANS DO NOT CORRELATE WITH THE LOAD CALCULATIONS, OVER
 CURRENT PROTECTION AND LOCATIONS.
 PLEASE SEE THE MISSING AIR HANDLER UNIT FOR 2ND FLOOR
 W/ DISCONNECT. 440.11, 110.26
 PLEASE SEE THE LOADS SHOWN ON CALCULATIONS EXCEED THAT
 OF THE RATING OF THE BRANCH CIRCUITS FEEDING EACH OF
 THESE SYSTEMS. PLEASE SEE 220.19, 240.4, 310.16,
 424.3B
 PLEASE SEE THE OVER CURRENT PROTECTION IS TO MEET THE
 MINIMUM FOR HEAT LOADS PER 424.3B (125% WHICH IS FOR
 OVER CURRENT PROTECTION).
 PLEASE ADJUST THE OCP, CONDUCTOR SIZES, LOCATIONS AND
 LOADS AS NEEDED.
  
 5) NOTE: PLEASE SEE THE LOAD, OVER CURRENT PROTECTION
 AND SIZE OF FEEDERS TO PANEL *B* DO NOT MEET THE
 REQUIREMENTS FOR THE LOADS.
 PLEASE ADJUST.
 240.4, 310.16, 408.4
  
 6) NOTE: PLEASE SHOW THE LOCATION OF PANEL *B*. 110.26,
 408.7, 240.24D
  
 7) NOTE: PLEASE CORRELATE CIRCUITING ON PLANS. PLEASE
 SEE THERE ARE SEVERAL CIRCUITS ON PANEL SCHEDULE(S)
 WHICH ARE NOT THE SAME AS ON PLANS.
 PLEASE SEE FOR EXAMPLE:
 B-7 ON PLANS IS FOR REFRIGERATOR, YET THE PANEL
 SCHEDULE SHOWS THIS AS THE DISHWASHER.
 B-9 NOT ON PANEL SCHEDULE YET SHOWN AS DISHWASHER ON
 PLANS.
 PLEASE SEE THERE ARE SOME OTHERS PLEASE BE SURE TO
 VERIFY ALL.
  
 8) NOTE: PLEASE SEE MISSING DISPOSAL ON PLANS. PLEASE
 BE SURE TO SEE 210.4B FOR REQUIRED 2-POLE BREAKER IF
 THE DISHWASHER AND DISPOSAL IS ON THE SAME YOKE.
 408.4.
 FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR
 REQUIRED CIRCUITING FOR DINING ROOM/AREA RECEPTACLE
 CIRCUITS. PLEASE SEE THE AREAS AS SPECIFIED IN 210.52B1
 ARE TO BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE ALSO SEE THAT THE LOAD SHALL BE
 FIGURED ON EACH OF THOSE CIRCUITS AT A MINIMUM OF
 1500VA FOR EACH. THIS INCLUDES ANY ABOVE THE MINIMUM
 FOR THE KITCHEN SMALL APPLIANCE CIRCUITS.
 PLEASE SEE AS NOTED IN SECTIONS, THESE MUST BE 20AMP
 AND #12 AWG.
 PLEASE ADJUST PLANS FOR THESE. (EXAMPLE CIRCUIT #33).
  
 10) NOTE: PLEASE SEE THERE ARE SEVERAL BATHROOM
 CIRCUITS WHICH DO NOT MEET 210.52D, 210.11C3. PLEASE
 SEE ONE CIRCUIT WHICH IS #22 MENTIONS THIS IS ALSO TO
 FEED HALL, WHICH IS NOT PERMITTED.
 PLEASE SEE THESE ARE SHOWN WITH THE REQUIRED #12
 HOWEVER NOT THE REQUIRED 20AMP BREAKER.
 PLEASE ADJUST ALL ON PLANS/PANEL SCHEDULES AS NEEDED.
 (19,22,37,38,39 ETC)
  
 11) NOTE: PLEASE SEE 210.12 FOR SMOKE ALARM CIRCUIT
 WHICH IS NOT SHOWN AS ARC FAULT PROTECTED AS REQUIRED.
 ALL OUTLETS ARE TO BE AFCI. PLEASE ADJUST AND LIST ON
 PANEL SCHEDULE.
  
 12) NOTE: PLEASE INDICATE THE AIC RATING FOR
 MAINS/PANELS/BREAKERS PER 110.9.
 FBC 106.1.2, 106.1.3, 106.3.5.4
  
 13) NOTE: PLEASE CLARIFY *UTILITY ROOM* CIRCUITS WHICH
 ARE SHOWN AS #12, 15AMP, AND GFI?
 THESE CIRCUITS 17 AND 23 ARE FEEDING OTHER AREAS ALSO.
  
 14) NOTE: PLEASE SEE WATER HEATER IS BEING SHOWN ON
 CIRCUITS 5/9 ON PLAN WHICH IS NOT POSSIBLE FOR
 220/240V. PLEASE SEE THE PANEL SCHEDULE AS THIS CALLS
 FOR 5/7.
 PLEASE ALSO SEE THE SYMBOL SHOWN FOR CONNECTION OF THE
 WATER HEATER LENDS THIS AS BEING PLUG IN CONNECTION.
 PLEASE SEE 422.30, 422.31 AS THIS UNIT IS REQUIRED TO
 BE HARDWIRED AND MAY NOT PLUG-IN.
 A DISCONNECT IS NOT REQUIRED WHEN THE PANEL IS WITHIN
 SIGHT, HOWEVER MAY BE INSTALLED.
  
 15) NOTE: PLEASE VERIFY IF THE CONDUIT FROM THE METER
 TO THE PANEL INSIDE IS UNDERGROUND/SLAB OR NOT. PLEASE
 SEE 230.70,230.71, AS A MAIN DISCONNECT WITH OVER
 CURRENT PROTECTION WOULD BE REQUIRED OUTSIDE IF MORE
 THAN 8FT OF UNPROTECTED CONDUCTORS ARE INSIDE THE
 DWELLING.
  
 16) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE ONLY:
 THE LOW VOLTAGE AS SHOWN ON PLANS WILL BE REQUIRED TO
 BE UNDER A SEPARATE PERMIT.
 PLEASE KNOW THESE PLANS MAY BE USED FOR REFERENCING AND
 A *TURN AROUND* PERMIT WILL BE ISSUED.
 ** THIS IS ONLY NOTED FOR INFORMATION TO THE OWNER.
  
 17) NOTE:
  
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-20 09:04:36NEW PLANS SUBMITTED ON 9/13/07