2007-10-24 12:11:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 **NEW PLANS DRAWN BY NEW DESIGNER**
  
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.)THE DESCRIPTION FOR 6X6 10/10 WWM HAS CHANGED TO
 6X6 W1.4XW1.4, SEE FBC R 506.2.4 EXCEPTION 2.THIS NOW
 REFERS TO CROSS SECTIONAL AREA RATHER THAN GAUGE;
 PLEASE REVISE FOUNDATION PLAN SHEET 4.
  
 4.)FOR THE SCREEN LANAI, EITHER PROVIDE ALL
 SPECIFICATIONS FOR THE SCREEN ENCLOSURE OR A SEPARATE
 PERMIT WILL BE REQUIRED.
  
 5.)THE TYPICAL STAIR DETAIL REFERS TO FBC1007.5.THE
 CORRECT CODE REFERENCES WILL BE FOUND IN FBC
 RESIDENTIAL.CHECK ALL CODE REFERENCES.
  
 6.)SHEET 2, WIND INFO, ITEM 6, INTERNAL PRESSURE
 COEFFICIENT IS "CH".WHAT IS THIS?
  
 7.)ROOF TRUSS PLANS WILL BE REQUIRED, REVIEWED BY
 ENGINEER OF RECORD, PRIOR TO INSTALLATION
 (INFORMATIONAL), FBC R 802.1.6.1.
  
 8.)SHOW GUARDRAIL AND STAIR RAIL HEIGHT, FBC R 311.5,
 312.STAIR RAIL HEIGHT IS SPECIFIED AS 32" OR 34", BUT
 DRAWN THE SAME HEIGHT AS THE GUARDRAIL, WHICH HAS A 34"
 MINIMUM HEIGHT REQUIREMENT.
  
 9.)SPECIFY DESIGN CRITERIA FOR THE GUARDRAIL AT THE
 BALCONY, FBC312.
  
 10.)DOOR 2, GARAGE TO HOUSE, SHEET 3, IS REQUIRED TO
 MEET THE REQUIREMENTS OF FBC R13-603.1ABC.1 (INSULATED
 OR SOLID CORE) AND R309.1 (FIRE RATING REQUIREMENTS).
  
 11.)SHOW SEPARATION BETWEEN GARAGE AND DWELLING AS
 REQUIRED BY FBC R 309.2.
  
 12.)SHEATHING FASTENING ON SHEET 5 IS IN CONFLICT
 WITH FBC TABLE 2304.9.1; 4" REQUIRED AT EDGE STRIP (NOT
 FOR GABLES ONLY).
  
 13.)SHEET 5 INCLUDES A FRAMING DETAIL FOR OPENINGS.
 AS THIS IS CBS CONSTRUCTION, WHERE IS THIS DETAIL
 APPLICABLE?PLEASE USE DETAIL REFERENCE MARKERS ON THE
 FLOOR PLAN.
  
 14.)PLEASE NOTE THAT NO ATTIC STORAGE WILL BE
 ALLOWED, SHEET 7 OR REVISE BOTTOM CHORD LIVE LOAD,
 FBC3.
  
 15.)SHEET 7, TRUSS ANCHOR SCHEDULE IS ILLEGIBLE.
  
 16.)SHEET 2, STAIR SECTTION, IS THE NOSING INCLUDED
 IN THE 10" TREAD, OR IS THIS A 10" TREAD AND AN
 ADDITIONAL 1" NOSING?FBC R 311.
  
 17.)SHEET 2, NOTE A, REVISE CODE REFERENCE AS FBC1007
 TO APPLICABLE RESIDENTIAL CODE SECTION.
  
 18.)PROVIDE A SOILS INVESTIGATION REPORT, TWO
 ORIGINALS.
  
 19.)PROVIDE COOLING LOAD CALCS FBC 13-607.1.ABC.1.
  
 20.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 21.)THE VALUE OF THIS PROJECT HAS BEEN ADJUSTED BASED
 SQUARE FOOT AREA USING THE ICC BUILDING VALUATION
 TABLES.