| 2007-10-24 12:11:22 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | **NEW PLANS DRAWN BY NEW DESIGNER** |
| | |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY PRIOR TO PERMIT ISSUANCE. |
| | THE PLANS MUST BE STAMPED AND THE |
| | RECEIPT ATTACHED TO THE APPLICATION. |
| | 561-233-5025 |
| | |
| | 3.)THE DESCRIPTION FOR 6X6 10/10 WWM HAS CHANGED TO |
| | 6X6 W1.4XW1.4, SEE FBC R 506.2.4 EXCEPTION 2.THIS NOW |
| | REFERS TO CROSS SECTIONAL AREA RATHER THAN GAUGE; |
| | PLEASE REVISE FOUNDATION PLAN SHEET 4. |
| | |
| | 4.)FOR THE SCREEN LANAI, EITHER PROVIDE ALL |
| | SPECIFICATIONS FOR THE SCREEN ENCLOSURE OR A SEPARATE |
| | PERMIT WILL BE REQUIRED. |
| | |
| | 5.)THE TYPICAL STAIR DETAIL REFERS TO FBC1007.5.THE |
| | CORRECT CODE REFERENCES WILL BE FOUND IN FBC |
| | RESIDENTIAL.CHECK ALL CODE REFERENCES. |
| | |
| | 6.)SHEET 2, WIND INFO, ITEM 6, INTERNAL PRESSURE |
| | COEFFICIENT IS "CH".WHAT IS THIS? |
| | |
| | 7.)ROOF TRUSS PLANS WILL BE REQUIRED, REVIEWED BY |
| | ENGINEER OF RECORD, PRIOR TO INSTALLATION |
| | (INFORMATIONAL), FBC R 802.1.6.1. |
| | |
| | 8.)SHOW GUARDRAIL AND STAIR RAIL HEIGHT, FBC R 311.5, |
| | 312.STAIR RAIL HEIGHT IS SPECIFIED AS 32" OR 34", BUT |
| | DRAWN THE SAME HEIGHT AS THE GUARDRAIL, WHICH HAS A 34" |
| | MINIMUM HEIGHT REQUIREMENT. |
| | |
| | 9.)SPECIFY DESIGN CRITERIA FOR THE GUARDRAIL AT THE |
| | BALCONY, FBC312. |
| | |
| | 10.)DOOR 2, GARAGE TO HOUSE, SHEET 3, IS REQUIRED TO |
| | MEET THE REQUIREMENTS OF FBC R13-603.1ABC.1 (INSULATED |
| | OR SOLID CORE) AND R309.1 (FIRE RATING REQUIREMENTS). |
| | |
| | 11.)SHOW SEPARATION BETWEEN GARAGE AND DWELLING AS |
| | REQUIRED BY FBC R 309.2. |
| | |
| | 12.)SHEATHING FASTENING ON SHEET 5 IS IN CONFLICT |
| | WITH FBC TABLE 2304.9.1; 4" REQUIRED AT EDGE STRIP (NOT |
| | FOR GABLES ONLY). |
| | |
| | 13.)SHEET 5 INCLUDES A FRAMING DETAIL FOR OPENINGS. |
| | AS THIS IS CBS CONSTRUCTION, WHERE IS THIS DETAIL |
| | APPLICABLE?PLEASE USE DETAIL REFERENCE MARKERS ON THE |
| | FLOOR PLAN. |
| | |
| | 14.)PLEASE NOTE THAT NO ATTIC STORAGE WILL BE |
| | ALLOWED, SHEET 7 OR REVISE BOTTOM CHORD LIVE LOAD, |
| | FBC3. |
| | |
| | 15.)SHEET 7, TRUSS ANCHOR SCHEDULE IS ILLEGIBLE. |
| | |
| | 16.)SHEET 2, STAIR SECTTION, IS THE NOSING INCLUDED |
| | IN THE 10" TREAD, OR IS THIS A 10" TREAD AND AN |
| | ADDITIONAL 1" NOSING?FBC R 311. |
| | |
| | 17.)SHEET 2, NOTE A, REVISE CODE REFERENCE AS FBC1007 |
| | TO APPLICABLE RESIDENTIAL CODE SECTION. |
| | |
| | 18.)PROVIDE A SOILS INVESTIGATION REPORT, TWO |
| | ORIGINALS. |
| | |
| | 19.)PROVIDE COOLING LOAD CALCS FBC 13-607.1.ABC.1. |
| | |
| | 20.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER |
| | OF RECORD, FBC*106.3.3. |
| | |
| | 21.)THE VALUE OF THIS PROJECT HAS BEEN ADJUSTED BASED |
| | SQUARE FOOT AREA USING THE ICC BUILDING VALUATION |
| | TABLES. |