Plan Review Notes
Plan Review Notes For Permit 06071334
Permit Number 06071334
Review Stop P
Sequence Number 3
Notes
Date Text
2007-02-06 08:05:26DENIED;
 1. SANITARY RISER DIAGRAM NOT TO CODE.
 A) AUTOMATIC CLOTHES WASHER DRAIN IS REQUIRED
 TO BE 3" AND MUST BE VENTED WITH C.O. AT 48". NOTE 10
 AND11 SHOULD BE SHOW ON THE RISER DIAGRAM.
 B) FIRST FLOOR SINK VENT TIED INTO SECOND
 FLOOR WASTE STACK. NOT A VENT.
 C) WATER CLOSET NOT VENTED.
 D) TUB NOT VENTED.
 E) TUB NOT VENTED.
 F)SHOWER NOT VENTED.
 G) SECOND FLOOR KITCHEN SINK MUST DISCHARGE
 DOWN STREAM OF THE BATHROOM GROUP. SEC.909.1.
 H) SECOND FLOOR MASTER BATHROOM NOT DRAWN
 CORRECTLY.
 I)USE PROPER NAMES FOR FIXTURES. (
 BATHROOMS HAVE LAVATORIES NOT SINKS).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695