Plan Review Notes
Plan Review Notes For Permit 06071334
Permit Number 06071334
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-21 09:50:02**** UNSAT ****
 3RD REVIEW UNDER PERMIT # 06071334
 6TH REVIEW FOR THIS SINGLE FAMILY HOUSE.(PREVIOUS#
 WAS 05041961
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW STILL NEED
 TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE THE NEC 2002. 220, 220.31, 220.16,
 220.14, 220.17, 210.52B1, 210.11C1, 210.11C2,ETCFOR
 LOAD CALCULATIONS, MINIMUM CIRCUITS, AND LOADS FOR EACH
 OF THOSE MINIMUM CIRCUITS.
 PLEASE SEE THE PREVIOUS COMMENTS FROM ALL OF THE
 PREVIOUS REVIEWS STATED THAT THE LOADS SHOWN ON THE
 PANEL SCHEDULE DID NOT CORRELATE WITH THE LOADS IN THE
 LOAD CALCULATIONS.
 PLEASE SEE AMPERAGES SHOWN ON THE PANEL SCHEDULE DO NOT
 CORRELATE WITH THE KVA/WATTAGE LOAD ON THE LOAD
 CALCULATIONS.
 PLEASE SEE LOADS OF 6AMPS IS BEING SHOWN FOR
 WASHER/LAUNDRY CIRCUIT, HOWEVER THIS DOES NOT CORRELATE
 WITH THE KVA ON CALCULATIONS
 PLEASE SEE THE DISHWASHER/DISPOSAL IS STILL BEING SHOWN
 ON THE SAME CIRCUIT AND IS SHOWN ON WITH THE DINING
 ROOM CIRCUIT. THE LOADS ON THE DISHWASHER AND DISPOSAL
 ARE MOST LIKELY DEDICATED CIRCUITS. THIS OFFICE HAS
 NEVER SEEN A DISHWASHER ON WITH THE DISPOSAL AND ALL
 THE OTHER RECEPTACLES AS SHOWN. PLEASE SEE THE DISPOSAL
 IS STILL ONLY BEING SHOWN HARDWIRED. IF THIS IS FED
 FROM THE SAME RECEPTACLE OUTLET AS THE DISHWASHER
 (SPLIT OUTLET) PLEASE SEE 210.4B
 PLEASE SEE MICROWAVE.
 PLEASE SEE MISSING SMALL APPLIANCE CIRCUIT DESIGNATIONS
 ON PANEL SCHEDULE. ONE CIRCUIT SEEMS TO BE SHOWN AS 2ND
 FLR GFI, INSTEAD OF SM APPL. PLEASE SEE THE OTHER
 CIRCUIT SHOWN IN THE KITCHEN IS SHOWN FEEDING THE
 REFRIGERATOR ONLY. PLANS SHOW ONE CIRCUIT FEEDING ALL
 COUNTER SPACE RECEPTS IN THE KITCHEN.
 PLEASE SEE THE LOAD FOR THE POOL PANEL IS BEING SHOWN
 AS 30AMPS, YET THE LOAD CALCULATIONS ONLY INDICATE
 2.2KW??
 PLEASE SEE GARAGE DOOR OPENER WHICH IS STILL BEING
 SHOWN ON WITH ALL OTHER RECEPTS IN THE GARAGE. PLEASE
 SEE MOTOR LOADS AS STATED ABOVE 220.14, 430.148.
 PLEASE SEE AS STATED IN THE PREVIOUS REVIEWS; PLEASE
 CORRELATE ALL OF THE LOADS ON PANEL SCHEDULE WITH THE
 LOADS BEING SHOWN IN THE LOAD CALCULATIONS.
 THE ABOVE ITEMS ARE NOT ALL POSSIBLE ITEMS AS THE NOTES
 MENTIONS; CODE COMPLIANCE FOR ALL SHALL BE MET.
 THE COMMENT RESPONSE FROM THE ARCHITECT MENTIONS ALL OF
 THESE WOULD BE ADDRESSED.
  
 2) NOTE: PLEASE SEE MISSING RECEPTACLE IN GUEST ROOM,
 THIS WAS ON PREVIOUS PLANS, HOWEVER IS NOW REMOVED. IF
 PLANS WERE OK WITH LOAD CALCULATIONS, THIS WOULD HAVE
 BEEN REDLINED. 210.52 2FT OF WALL SPACE.
  
 3) NOTE: PLEASE SEE THE AHU'S IN THE FIRST FLOOR CLOSET
 AND 2ND FLOOR ATTIC ARE STILL BEING SHOWN WITH 220V
 RECEPTACLES? THIS WAS GONE OVER ON THE MEETING WITH THE
 ARCHITECT AND THE DESIGNER. THE RECEPTACLE WAS GOING TO
 BE REMOVED, HOWEVER STILL SHOWN ON PLANS. PLEASE SEE
 THIS WOULD HAVE BEEN REDLINED, HOWEVER SEE NOTE #1.
 THE AHU'S ARE TO BE HARDWIRED TO DISCONNECTS, THESE ARE
 NOT TO BE CORD AND PLUG CONNECTED. THE SIGNED AND
 SEALED COMMENT RESPONSE FROM THE ARCHITECT MENTIONS
 WOULD BE ADDRESSED AND CORRECTED.
 4220.30, 422.30, 440.11.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEWS REQUESTED ALL
 CIRCUITING ON PLANS TO CORRELATE WITH PANEL SCHEDULE.
 PLEASE SEE DRYER IS STILL BEING SHOWN WITH A RECEPTACLE
 WHICH FEEDS THE GUEST ROOM?
 (CIRCUIT #20).
 408.4, 310.16, 240.4,
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE RISER SHOWS POOL SUB PANEL BEING
 30AMP, YET THIS IS BEING FED FROM A 40AMP BREAKER ON
 THE MAIN PANEL. PLEASE CORRELATE THE LOADS (AS NOTED
 ABOVE IN NOTE #1), PLEASE CORRELATE THE SIZE OF THE
 PANEL AND ANY OTHER ASPECTS TO THIS.
 RESPONSE MENTIONS THIS WOULD BE CORRECTED AS THIS
 COMMENT WAS IN PREVIOUS REVIEWS;, HOWEVER PLEASE SEE
 THIS IS STILL IN NEED OF COORDINATION.
 310.16, 240.4, 220, ETC.
  
 6) NOTE: PLEASE SEE AS GIVEN NOTICE IN THE PREVIOUS
 REVIEWS, A 4X FEE HAS NOW BEEN ASSESSED TO THE DESIGN
 PROFESSIONAL FOR REPEAT CODE COMPLIANCE COMMENTS PER
 553.80(2)(B).
 PLEASE SEE THE FEE OF $2820.00 HAS NOW BEEN ASSESSED TO
 THE DESIGN PROFESSIONAL AND IS NOT THE RESPONSIBILITY
 OF THE CONTRACTOR OR THE OWNER OF PROPERTY.
 ONE COPY OF THE ELECTRICAL PLANS IS BEING RETAINED AND
 WILL BE PLACED WITH THE OTHER PREVIOUS FIVE SETS OF
 PLANS PREVIOUSLY RETAINED IN FILE. THESE PLANS WILL BE
 FORWARDED TO THE STATE BOARD OF ARCHITECT'S LEGAL
 COUNSEL ONCE ALL REVIEWS ARE COMPLETED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]