2006-10-27 13:07:24********** UNSAT 2ND REVIEW UNDER 06071334
 ***************
 5TH REVIEW FOR PROJECT**
  
 1) NOTE:PLEASE SEE THAT THIS ISNOW THE
 5TH REVIEW FOR THIS PROJECT. PLANS
 ORIGINALLY CAME IN UNDER A "PLAN REVIEW"
 FOR THREE REVIEWS UNDER #05041961 AND
 NOW ARE BEING SUBMITTED FOR PERMIT.
 PLEASE SEE MANY OF THE FOLLOWING
 COMMENTS ARE FROM ALL PREVIOUS
 ELECTRICAL REVIEWS.
 ** PLEASE KNOW ONCE AGAIN PLANS ARE BEING RETAINED.
 PLEASE SEE OTHER
 POSSIBLE COMMENTS FROM OTHER TRADES.
 PLANS WILL BE REVIEWED BY THE SAME
 REVIEWERS AS PREVIOUSLY REVIEWED.
 PLEASE BE AWARE THAT ONE COMPLETE SET OF
 PLANS ARE BEING RETAINED AND WILL BE ALL
 SETS OF PLANS PREVIOUSLY RETAINED. ONCE
 ALL REVIEWS ARE COMPLETE PLANS WILL BE
 FORWARDED TO THE STATE BOARD OF
 ARCHITECT'S AND STATE'S LEGAL COUNSEL TO
 THE BOARD. THESE PLANS WILL NOW HAVE
 BEEN REVIEWED FOUR TIMES FOR A SINGLE
 FAMILY HOUSE WITH MOST OF THE SAME
 COMMENTS FOR ELECTRICAL NOT ADDRESSED.
 PLEASE SEE FS 553.80(2)(B).
 PLEASE KNOW, IF PLANS COME BACK WITH ANY OF THE SAME
 COMMENTS FOE CODE COMPLIANCE NOT ADDRESSED, A 4X FEE
 WILL BE ASSESSED.
 PLEASE SEE
 FS 481.221(4)
  
 2) NOTE: OK.
  
 3) NOTE:NO, SOME CIRCUITS SHOWN BLANK ON SCHEDULE FOR
 CONDUCTOR AND BREAKER SIZES FOR THIS?
 PLEASE ALSO SEE PREVIOUS NOTES WHICH MENTIONS THE BATH
 CIRCUIT WITH THE GFI RECEPT MAY NOT BE PART OF ANY
 OTHER DEVICES/OUTLETS OUTSIDE THE BATH ROOM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52D, 210.11C3
 FOR CIRCUITING OF BATH(S). PLEASE SEE
 MULTIPLE BATHS MAY NOT BE FED FROM THE
 SAME CIRCUIT WHEN FEEDING BATH LTS AND
 RECEPTS.
 PLEASE ALSO SEE THE REQUIRED DEDICATED
 BATH CIRCUIT(S) ARE ALSO SHOWN FEEDING
 OTHER AREAS? (HALL, CLOSETS ETC).
 PLEASE SEE PLANS SHOW THIS IS VIOLATION
 OF CODES ABOVE.
  
 4) NOTE: NO, SAME NOTE>
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE RISER AND
 PANEL SCHEDULE FOR FUTURE POOL PANEL.
 TWO SETS OF FEEDER SIZE ARE SHOWN??
 #8'S ? #6'S?
 215.5, FBC106.1.2
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE:NO, SAME NOTE >
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MIN DISCONNECT
 CLEARANCES PER 110.26 FOR A/C CU.
  
 8) NOTE:NO/OK, PLEASE SEE ACCESS SEEMS TO BE
 ADDRESSED, HOWEVER PLEASE SEE THAT THE UNITS ARE NOW
 BEING SHOWN AND NOTED HAVING RECEPTS FOR UNIT??? PLEASE
 SEE 440.11,110.26 AS DISCONNECTS ARE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MECHANICAL COMMENTS
 AS AHU SHOWN IN ATTIC IS MORE THAN 6'
 AWAY FROM WHAT IS SHOWN AS THE ATTIC
 ACCESS ON PLANS.
 PLEASE ALSO SEE MISSING LT AND RECPT.210.70,210.63
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: NO, LOAD CALCULATIONS DO NOT MEET CODE.
 PLEASE SEE NEC 220.31 , 220.
 CAN NOT TAKE DE-RATINGS FOR SMALL APPLIANCE CIRCUITS.
 PLEASE SEE NOW WASHER/LAUNDRY CIRCUIT IS BEING SHOWN AS
 1200 VA. PLEASE SEE 220.16, 210.11C2 FOR MIN VA.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE NEC FOR LOAD CALCULATIONS. IT IS NOT
 CLEAR WHERE AND
 HOW THESE FIGURES ARE DERIVED AS THE
 DERATING SHOWN DO NOT APPEAR IN THE
 CODE. PLEASE SEE DIFFERENT PERCENTAGES
 ARE BEING SHOWN WHICH ARE NOT PERMITTED.
 PLEASE SEE 220.
 PLEASE ALSO SEE MANY LOADS (AMERAGES)
 SHOWN ON PANEL SCHEDULE DO NOT CORRELATE
 WITH THE KW RATINGS SHOWN ON LOAD
 CALCULATIONS.
 PLEASE SEE A/C#1, A/C #2, DRYER, RANGE
 ETC, HOW AND WHERE DO THESE AMPERAGE'S
 COME FROM. PLEASE SEE THE KW RATING IS
 DIVIDED BY THE VOLTAGE TO ARRIVE AT THE
 AMPERAGE AND THE FIGURES SHOWN JUST
 DON'T ADD UP.????
 PLEASE SEE OTHER LOADS WHERE LOADS ARE
 TAKEN AT 40%?? PLEASE INDICATE HOW AND
 WHERE IN THE NEC PERMITS THESE AT 40%??
 PLEASE SEE NEC 2002 ART 220.
 PLEASE ALSO CLARIFY HOW THE LOADS SHOWN
 OFGENERAL LIGHTING AND RECEPT LOADS
 ARE DERIVED. AN AMPERAGE LOAD IS SHOWN
 FOR EACH OF THESE??
  
 12) NOTE: OK.
  
 13) NOTE:NO, DISC SHOWN, HOWEVER DO NOT MEET 110.26.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW REQUIRED
 DISCONNECTS FOR CU'S 440.11 AND PLEASE
 SEE 110.26 FIR MIN CLEARANCE.
  
 14) NOTE: OK.
  
 15) NOTE:OK.
  
 *** NEW NOTE **
  
 16) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) ATTACHED.
  
 17) NOTE: PLEASE KNOW, IN NO CASE CAN WHITE OUT OR HAND
 WRITTEN CHANGES BE PLACED ON PLANS SIGNED , DATED AND
 SEALED BY A DESIGN PROFESSIONAL.
 FS 481/471
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW