| 2006-11-06 13:56:43 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | PLAN CHECK #05041961 |
| | |
| | COMMENTS FROM THE PREVIOUS REVIEWS; |
| | NUMBERING TO REMAIN THE SAME FOR |
| | CONSISTENCY.NOTE THAT CODE REFERENCE |
| | NUMBERS HAVE CHANGED AS THE FIRST REVIEW |
| | WAS DONE ON FBC2001, SECOND AND THIRD REVIEWS ON |
| | FBC2004. |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY PRIOR TO PERMIT ISSUANCE. |
| | THE PLANS MUST BE STAMPED AND THE |
| | RECEIPT ATTACHED TO THE APPLICATION. |
| | 561-233-5025 |
| | |
| | 3.-5.)ADDRESSED. |
| | |
| | 6.)ENERGY CALCS REQUIRED, FBC11-101.2. |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALC, FBC11-103.1.2. |
| | |
| | 7.)A9.0 IS NOT LEGIBLE. |
| | IT ALSO CONTAINS MANY INCORRECT CODE REFERENCES; FOR |
| | INSTANCE, BOCA (GOVERNING CODE IS FBC2004) AND |
| | ACI530.1-95 (USE CURRENT REFERENCES).CHECK ALL |
| | SPECIFICATIONS. |
| | |
| | 8.-41.)ADDRESSED. |
| | |
| | 42.)SHOW POSITIVE DRAINAGE FBC R401.3, FBC*109.3.10. |
| | THE TYPICAL WALL SECTION ON A8.0 SHOWS A SLOPE AWAY |
| | FROM THE BUILDING, BUT AT 5' AWAY FROM THE PROPERTY |
| | LINE DOESN'T THIS CAUSE THE WATER TO DUMP ONTO THE |
| | ADJACENT PARCEL?PLEASE ADDRESS DRAINAGE ON THE SITE |
| | PLAN. |
| | |
| | 43-55.)ADDRESSED. |
| | |
| | NEW COMMENT: |
| | |
| | 56.)DESIGN CRITERIA FOR TRUSSES IS NOT CLEAR.A9.0 |
| | STATES 20PSF LIVE, 10PSF DEAD BOTTOM CHORD; A7.0 NOTE |
| | STATES "20PSF DEAD LOAD 10PSF". |
| | |
| | 57.)A9.0 STILL SPECIFIES SHEATHING NAILING OF 6" ON |
| | EDGES, 8"IN THE FIELD.FLOOR SHEATHING NAILING IS IN |
| | CONFLICT WITH OTHERS SPECIFICATIONS ON THE PLAN.THE |
| | SHEET IS DIFFICULT TO READ.MAKE THIS SHEET LEGIBLE IF |
| | IT IS REQUIRED FOR CODE COMPLIANCE, AND CHECK THAT ALL |
| | NOTES ARE CODE COMPLIANT, CURRENT, REFERRING TO CURRENT |
| | GOVERNING CODE, AND SPECIFICATIONS ARE CONSISTENT WITH |
| | OTHER SPECIFICATIONS ON THE PLAN. |
| | |
| | 58.)PRODUCT APPROVALS REQUIRED FOR COMPONENTS AND |
| | CLADDING.PRODUCT APPROVALS ARE TO BE APPROVED BY |
| | DESIGNER OF RECORD, FBC*106.3.3. |