| 2006-07-25 00:00:00 | DENIED; | | | 1.SANITARY RISER DIAGRAM IS NOT TO CODE; | | | A)FIRST FLOOR REVENTS MUST EXTEND 6" | | | ABOVE THE HIGHEST FIXTURE ON THE | | | SECOND FLOOR BEFORE REVENTING INTO | | | THE VENT STACK. | | | B)TOILET ON FIRST FLOOR CANNOT BE | | | INSTALLED DIRECTLY INTO THE BUILD- | | | DRAIN, NOT VENTED PROPERY. | | | C)WATER HEATER IS NOT PART OF THE | | | SANITARY SYSTEM AND SHOULD NOT | | | BE SHOWN ON THE RISER DIAGRAM. | | | D)AUTOMATIC CLOTHES WASHER DRAIN, | | | STAND PIPE AND VENT WITH CLEANOUT | | | NOT DRAWN. DRAIN FOR THE W/M IS | | | REQUIRED TO BE 3" AND A CLEANOUT TO | | | BE AT 48" AFF. SEE SEC. 406.3 AND | | | 708..3.4. | | | E)DISHWASHER MUST DICHARGE INDIRECTLY | | | INTO THE DRAINAGE SYSTEM. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|