2006-07-25 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM IS NOT TO CODE;
 A)FIRST FLOOR REVENTS MUST EXTEND 6"
 ABOVE THE HIGHEST FIXTURE ON THE
 SECOND FLOOR BEFORE REVENTING INTO
 THE VENT STACK.
 B)TOILET ON FIRST FLOOR CANNOT BE
 INSTALLED DIRECTLY INTO THE BUILD-
 DRAIN, NOT VENTED PROPERY.
 C)WATER HEATER IS NOT PART OF THE
 SANITARY SYSTEM AND SHOULD NOT
 BE SHOWN ON THE RISER DIAGRAM.
 D)AUTOMATIC CLOTHES WASHER DRAIN,
 STAND PIPE AND VENT WITH CLEANOUT
 NOT DRAWN. DRAIN FOR THE W/M IS
 REQUIRED TO BE 3" AND A CLEANOUT TO
 BE AT 48" AFF. SEE SEC. 406.3 AND
 708..3.4.
 E)DISHWASHER MUST DICHARGE INDIRECTLY
 INTO THE DRAINAGE SYSTEM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695