| Date |
Text |
| 2006-07-25 00:00:00 | ********** UNSAT *************** |
| | |
| | 1) NOTE:PLEASE SEE THEAT THIS IS THE |
| | 4TH REVIEW FOR THIS PROJECT. PLANS |
| | ORIGINALLY CAME IN UNDER A "PLAN REVIEW" |
| | FOR THREE REVIEWS UNDER #05041961 AND |
| | NOW ARE BEING SUBMITTED FOR PERMIT. |
| | PLEASE SEE MANY OF THE FOLLOWING |
| | COMMENTS ARE FROM ALL PREVIOUS |
| | ELECTRICAL REVIEWS. PLEASE SEE OTHER |
| | POSSIBLE COMMENTS FROM OTHER TRADES. |
| | PLANS WILL BE REVIEWED BY THE SAME |
| | REVIEWERS AS PREVIOUSLY REVIEWED. |
| | ************************************* |
| | PLEASE BE AWARE THAT ONE COMPLETE SET OF |
| | PLANS ARE BEING RETAINED AND WILL BE ALL |
| | SETS OF PLANS PREVIOUSLY RETAINED. ONCE |
| | ALL REVIEWS ARE COMPLETE PLANS WILL BE |
| | FORWARDED TO THE STATE BOARD OF |
| | ARCHITECT'S AND STATE'S LEGAL COUNSEL TO |
| | THE BOARD. THESE PLANS WILL NOW HAVE |
| | BEEN REVIEWED FOUR TIMES FOR A SINGLE |
| | FAMILY HOUSE WITH MOST OF THE SAME |
| | COMMENTS FOR ELECTRICAL NOT ADDRESSED. |
| | PLEASE SEE FS 553.80(2)(B). |
| | PLEASE SEE I AM ATTACHING ALL REVIEWS |
| | FOR ALL TRADES DONE UNDER 05041961 AND |
| | NEW COMMENTS UNDER 06071334. |
| | FS 481.221(4) |
| | |
| | 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | THIS WAS REQUESTED ON ALL PREVIOUS |
| | REVIEWS. |
| | |
| | 3) NOTE: PLEASE SEE 210.52D, 210.11C3 |
| | FOR CIRCUITING OF BATH(S). PLEASE SEE |
| | MULTIPLE BATHS MAY NOT BE FED FROM THE |
| | SAME CIRCUIT WHEN FEEDING BATH LTS AND |
| | RECEPTS. |
| | PLEASE ALSO SEE THE REQUIRED DEDICATED |
| | BATH CIRCUIT(S) ARE ALSO SHOWN FEEDING |
| | OTHER AREAS? (HALL, CLOSETS ETC). |
| | PLEASE SEE PLANS SHOW THIS IS VIOLATION |
| | OF CODES ABOVE. |
| | |
| | 4) NOTE: PLEASE CORRELATE RISER AND |
| | PANEL SCHEDULE FOR FUTURE POOL PANEL. |
| | TWO SETS OF FEEDER SIZE ARE SHOWN?? |
| | #8'S ? #6'S? |
| | 215.5, FBC106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN DISCONNECT |
| | TO PANEL "A". 250.24B, 250.110,250.122 |
| | |
| | 6) NOTE: PLEASE SEE MISSING REQUIRED |
| | FOOTER STEEL AS PART OF THE GROUNDING |
| | ELECTRODE SYSTEM. 250.50 |
| | |
| | 7) NOTE: PLEASE SEE MIN DISCONNECT |
| | CLEARANCES PER 110.26 FOR A/C CU. |
| | |
| | 8) NOTE: PLEASE SEE MECHANICAL COMMENTS |
| | AS AHU SHOWN IN ATTIC IS MORE THAN 6' |
| | AWAY FROM WHAT IS SHOWN AS THE ATTIC |
| | ACCESS ON PLANS. |
| | PLEASE ALSO SEE MISSING LT AND RECPT.210.70,210.63 |
| | |
| | 9) NOTE: PLEASE THAT THE FOLLOWING |
| | MINIMUM CODES ARE REFERENCED ON THE |
| | PLANS. |
| | 2002 NFPA-70 (NEC), 2002 NFPA-72 . |
| | |
| | 10) NOTE: PLEASE SEE SD'S ARE STILL |
| | BEING SHOWN ON MULTIPLE CIRCUITS???? |
| | PLEASE KNOW, SD'S ARE REQUIRED TO BE |
| | 120V W/ BATTERY BACK AND WIRED "INLINE" |
| | WITH EACH OTHER. PLEASE EXPLAIN HOW THIS |
| | IS POSSIBLE AS SHOWN WITH SD'S BEING |
| | SHOWN ON AT LEAST FOUR DIFFERENT |
| | CIRCUITS?? |
| | 11.5.1.1, 11.8.3 NFPA-72 |
| | |
| | 11) NOTE: PLEASE SEE THE NEC FOR LOAD CALCULATIONS. IT |
| | IS NOT CLEAR WHERE AND |
| | HOW THESE FIGURES ARE DERIVED AS THE |
| | DERATING SHOWN DO NOT APPEAR IN THE |
| | CODE. PLEASE SEE DIFFERENT PERCENTAGES |
| | ARE BEING SHOWN WHICH ARE NOT PERMITTED. |
| | PLEASE SEE 220. |
| | PLEASE ALSO SEE MANY LOADS (AMERAGES) |
| | SHOWN ON PANEL SCHEDULE DO NOT CORRELATE |
| | WITH THE KW RATINGS SHOWN ON LOAD |
| | CALCULATIONS. |
| | PLEASE SEE A/C#1, A/C #2, DRYER, RANGE |
| | ETC, HOW AND WHERE DO THESE AMPERAGE'S |
| | COME FROM. PLEASE SEE THE KW RATING IS |
| | DIVIDED BY THE VOLTAGE TO ARRIVE AT THE |
| | AMPERAGE AND THE FIGURES SHOWN JUST |
| | DON'T ADD UP.???? |
| | PLEASE SEE OTHER LOADS WHERE LOADS ARE |
| | TAKEN AT 40%?? PLEASE INDICATE HOW AND |
| | WHERE IN THE NEC PERMITS THESE AT 40%?? |
| | PLEASE SEE NEC 2002 ART 220. |
| | PLEASE ALSO CLARIFY HOW THE LOADS SHOWN |
| | OFGENERAL LIGHTING AND RECEPT LOADS |
| | ARE DERIVED. AN AMPERAGE LOAD IS SHOWN |
| | FOR EACH OF THESE?? |
| | |
| | 12) NOTE: PLEASE SEE MISSING RECEPT PER |
| | 210.52 IN UTILITY AREA. |
| | |
| | 13) NOTE: PLEASE SHOW REQUIRED |
| | DISCONNECTS FOR CU'S 440.11 AND PLEASE |
| | SEE 110.26 FIR MIN CLEARANCE. |
| | |
| | 14) NOTE: PLEASE SEE RECEPT SHOWN FOR |
| | WATER HEATER, HOWEVER THIS IS REQUIRED |
| | TO BE HARDWIRED W/ DISCONNECT. |
| | 422.30,422.31. |
| | |
| | 15) NOTE: PLEASE VERIFY THE OCP SHOWN |
| | FOR DRYER. THIS IS A 5KW UNIT AND SHOWS |
| | 40A OCP?. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTRUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |