Plan Review Notes
Plan Review Notes For Permit 06071334
Permit Number 06071334
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 PLAN CHECK #05041961
  
 COMMENTS FROM THE PREVIOUS REVIEWS;
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.NOTE THAT CODE REFERENCE
 NUMBERS HAVE CHANGED AS THE FIRST REVIEW
 WAS DONE ON FBC2001, SECOND REVIEW ON
 FBC2004.
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.-5.)ADDRESSED.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
 THE FRAME WALLS AND THE FLOOR CEILING
 ASSEMBLY ARE NOT SHOWN.THERE ARE
 INTERIOR ADJACENT WALLS AND EXTERIOR
 FRAME WALLS.THE BLOCK WALL ON THE
 ENERGY CALC SHOWS 0 INSULATION;
 INSULATION REQUIRED BETWEEN CONDITIONED
 AND UNCONDITIONED SPACE, AND IN CONFLICT
 WITH THE PLAN.
  
 7.)A7.0, PROJECT DATA, IS NOT LEGIBLE.
 DESIGN PRESSURES ARE NOT LEGIBLE.
 FBC1606.1.7 IS NOT THE CORRECT CODE
 REFERENCE; PLEASE REMOVE.
  
 8.-19.)ADDRESSED.
  
 20.)WHAT IS THE CONSTRUCTION OF THE
 CABANA WALLS?IT DOES NOT APPEAR TO BE
 BLOCK.PROVIDE A DETAIL."STUCCO ON
 INSULATED WALLS" IS NOT A SUFFICIENT
 DETAIL.
  
 21.)SEE FBC R302.1,302.2, BAY WINDOW
 MUST BE OVER 3' FROM THE PROPERTY LINE.
 NOTE THAT THE ARCHITECT'S SITE PLAN
 SHOWS THE BAY WINDOW 3' FROM THE
 PROPERTY LINE.NO OPENINGS ALLOWED 3'
 FROM THE PROPERTY LINE.THIS IS IN
 CONFLICT WITH THE SURVEY WHICH SHOWS
 3.5' FROM THE PROPERTY LINE.3.5' IS
 ACCEPTABLE.
  
 22-26.)ADDRESSED.
  
 27.)REGARDING THE WALL BETWEEN THE
 GARAGE AND LAUNDRY AREA, FROM PREVIOUS
 CORRECTION LIST: THE FRAME WALL SHOWS
 "SOUND INSULATION", MUST HAVE R VALUE
 SPECIFIED FBC13-602.
  
 28.-41.)ADDRESSED.
  
 42.)SHOW POSITIVE DRAINAGE FBC R401.3,
 FBC*109.3.10.
  
 43-46.)ADDRESSED.
  
 46.)THE GARAGE BEAM DETAIL SHOWS EMPTY
 SPACE ABOVE THE BEAM.HOW WILL THIS BE
 STRUCTURALLY CONTINUOUS?
  
 47.)PROVIDE A DETAIL FOR THE EXTERIOR
 FRAME WALL.
  
 NOT ADDRESSED.
  
 NEW COMMENTS, 3RD REVIEW:
  
 48.)A7.0 REFERS TO ASCE7-98, CORRECT
 REFERENCE IS ASCE7-02, FBC35.
  
 49-53.) ADDRESSED.
  
 NEW COMMENT:
  
 54.)R403.1.4, EXTERIOR FOOTINGS TO BE
 12" BELOW GRADE.
  
 55.)TWO COPIES OF ALL DOCUMENTS
 REQUIRED.
  
  
  