| 2006-08-08 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | PLAN CHECK #05041961 |
| | |
| | COMMENTS FROM THE PREVIOUS REVIEWS; |
| | NUMBERING TO REMAIN THE SAME FOR |
| | CONSISTENCY.NOTE THAT CODE REFERENCE |
| | NUMBERS HAVE CHANGED AS THE FIRST REVIEW |
| | WAS DONE ON FBC2001, SECOND REVIEW ON |
| | FBC2004. |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY PRIOR TO PERMIT ISSUANCE. |
| | THE PLANS MUST BE STAMPED AND THE |
| | RECEIPT ATTACHED TO THE APPLICATION. |
| | 561-233-5025 |
| | |
| | 3.-5.)ADDRESSED. |
| | |
| | 6.)ENERGY CALCS REQUIRED, FBC11-101.2. |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALC, FBC11-103.1.2. |
| | |
| | THE FRAME WALLS AND THE FLOOR CEILING |
| | ASSEMBLY ARE NOT SHOWN.THERE ARE |
| | INTERIOR ADJACENT WALLS AND EXTERIOR |
| | FRAME WALLS.THE BLOCK WALL ON THE |
| | ENERGY CALC SHOWS 0 INSULATION; |
| | INSULATION REQUIRED BETWEEN CONDITIONED |
| | AND UNCONDITIONED SPACE, AND IN CONFLICT |
| | WITH THE PLAN. |
| | |
| | 7.)A7.0, PROJECT DATA, IS NOT LEGIBLE. |
| | DESIGN PRESSURES ARE NOT LEGIBLE. |
| | FBC1606.1.7 IS NOT THE CORRECT CODE |
| | REFERENCE; PLEASE REMOVE. |
| | |
| | 8.-19.)ADDRESSED. |
| | |
| | 20.)WHAT IS THE CONSTRUCTION OF THE |
| | CABANA WALLS?IT DOES NOT APPEAR TO BE |
| | BLOCK.PROVIDE A DETAIL."STUCCO ON |
| | INSULATED WALLS" IS NOT A SUFFICIENT |
| | DETAIL. |
| | |
| | 21.)SEE FBC R302.1,302.2, BAY WINDOW |
| | MUST BE OVER 3' FROM THE PROPERTY LINE. |
| | NOTE THAT THE ARCHITECT'S SITE PLAN |
| | SHOWS THE BAY WINDOW 3' FROM THE |
| | PROPERTY LINE.NO OPENINGS ALLOWED 3' |
| | FROM THE PROPERTY LINE.THIS IS IN |
| | CONFLICT WITH THE SURVEY WHICH SHOWS |
| | 3.5' FROM THE PROPERTY LINE.3.5' IS |
| | ACCEPTABLE. |
| | |
| | 22-26.)ADDRESSED. |
| | |
| | 27.)REGARDING THE WALL BETWEEN THE |
| | GARAGE AND LAUNDRY AREA, FROM PREVIOUS |
| | CORRECTION LIST: THE FRAME WALL SHOWS |
| | "SOUND INSULATION", MUST HAVE R VALUE |
| | SPECIFIED FBC13-602. |
| | |
| | 28.-41.)ADDRESSED. |
| | |
| | 42.)SHOW POSITIVE DRAINAGE FBC R401.3, |
| | FBC*109.3.10. |
| | |
| | 43-46.)ADDRESSED. |
| | |
| | 46.)THE GARAGE BEAM DETAIL SHOWS EMPTY |
| | SPACE ABOVE THE BEAM.HOW WILL THIS BE |
| | STRUCTURALLY CONTINUOUS? |
| | |
| | 47.)PROVIDE A DETAIL FOR THE EXTERIOR |
| | FRAME WALL. |
| | |
| | NOT ADDRESSED. |
| | |
| | NEW COMMENTS, 3RD REVIEW: |
| | |
| | 48.)A7.0 REFERS TO ASCE7-98, CORRECT |
| | REFERENCE IS ASCE7-02, FBC35. |
| | |
| | 49-53.) ADDRESSED. |
| | |
| | NEW COMMENT: |
| | |
| | 54.)R403.1.4, EXTERIOR FOOTINGS TO BE |
| | 12" BELOW GRADE. |
| | |
| | 55.)TWO COPIES OF ALL DOCUMENTS |
| | REQUIRED. |
| | |
| | |
| | |