| 2007-03-06 10:14:25 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS: |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | THE FOLLOWING ARE FROM THE PREVIOUS REVIEW DATED |
| | 8/21/06 |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. NO,SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: PLEASE PROVIDE MANUFACTURER SHEETS FOR THE |
| | FOLLOWING. |
| | A} MP REGULATOR |
| | B} GENERATOR |
| | 9. OK, N/A |
| | 10. OK, N/A |
| | |
| | THE FOLLOWING ARE NEW COMMENTS: |
| | |
| | 11. PLEASE PROVIDE 2 COPIES OF SITE PLAN OR SURVEY AT |
| | THE TIME OF PERMIT APPLICATION THAT INCLUDE THE |
| | FOLOWING INFORMATION. |
| | A} THE CLEARLY MARKED PROPOSED LOCATION FOR THE |
| | INSTALLATION OF THE GENERATOR. |
| | B} INDICATION OF ALL DIMENTIONS FROM PROPERTY LINES |
| | AND DISTANCES FROM ADJACENT DWELLING STRUCTURES. |
| | C} INDICATION THAT THE GENERATOR EXHAUST IS NOT |
| | INSTALLED CLOSER THAN TEN FEET FROM ANY OPENING INTO |
| | THE DWELLING STRUCTURE. THIS INCLCES DOORS, WINDOWS AND |
| | ATTIC VENTILATION OPENINGS. |
| | |
| | 12. PLEASE SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS/CUT SHEETS FOR GENERATOR, SHOWING |
| | LISTINGS FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY (NRTL). PLEASE INCLUDE INSTALLATIN |
| | INSTRUCTIONS INDICATING CLEARENCES TO DWELLINGS. |
| | |
| | END OF COMMENTS: |
| | |