| Plan Review Notes For Permit 06071278 |
| Permit Number |
06071278 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-05 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE ILLUSTRATE BUILDING OPENINGS | | | AS IT RELATES TO THE LOCATION OF THE | | | GENERATOR. | | | | | | 2) WORK TO COMPLY WITH NFPA 110, | | | STANDARD FOR EMERGENCY AND STANDBY POWER | | | SYSTEMS. | | | | | | 3) PLEASE PROVIDE VERIFICATION AS TO | | | FUEL SOURCE, NATURAL GAS OR PROPANE. | | | SPEC SHEETS INDICATE SEVERAL OPTIONS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|