| 2006-08-09 00:00:00 | ***** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE THE 2002 NEC. |
| | 225.31-225.39, 230.72 |
| | PLEASE SEE THAT THIS OFFICE IS UNABLE TO |
| | VERIFY THIS AT THIS TIME. |
| | |
| | 2) NOTE: PLEASE INDICATE ANY AND ALL |
| | CONTINUOOUS LOADS AT 125%. |
| | 215.3,230.42 ETC. |
| | |
| | 3) NOTE: PLEASE UPDATE PANEL SCHEDULES |
| | AS THE PANELS DID NOT SEEM TO GET ALL |
| | THE NEW CIRCUITS. "E". 408.4 |
| | 106.1.2 FBC ADMIN SECT |
| | |
| | 4) NOTE: PLEASE PROVIDE A LAYOUT OF ALL |
| | SERVICE EQUIPMENT. PLEASE PROVIDE AN |
| | OVERVIEW AS NO ELECTRICAL EQUIPMENT IS |
| | SHOWN. CAN NOT VERIFY ITEMS IN NOTE #1 |
| | AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SUBMIT SPECS/CUT SHEETS |
| | FROM THE MANUFACTURE FOR THE ATS. |
| | 110.3, 90.8 |
| | PLEASE ALSO SUBMIT THE SPECS/SHEETS FOR |
| | THE WP HOUSING AS THE GEN DOES NOT SHOW |
| | THIS. |
| | |
| | 6) NOTE: PLEASE CORRLELATE THE OCP FOR |
| | THE NEW TRANSFORMER AS THE PANEL SHOWS |
| | ONE AND THE RISER SHOWS ANOTHER. |
| | 450.3, |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE PROVIDE GROUNDING OF THE |
| | NEW TRANSFORMER. |
| | 250.30,250.20,250.66 ETC |
| | |
| | 8) NOTE: PLEASE SEE PLANS/DRAWINGS ARE |
| | NOT REQUIRED TO BE NOTARIZED, HOWEVER IF |
| | THEY ARE THEN THEY NEED TO BE CORRECTLY |
| | NOTARIZED AS REQUIRED PERFS 117.05 |
| | PLEASE KNOW ONLY A STAMP AND SIGNATURE |
| | IS NOT ACCEPTABLE. |
| | |
| | 9) NOTE: PLEASE SEE EXISTING MDP, IS |
| | BEING SHOWN AS MLO. PLEASE CLARIFY AS |
| | THIS CONTAINS MANY MORE THAN 6 MEANS OF |
| | DISCONNECT. 230.70 |
| | PLEASE KNOW, ALL DISCONNECTING MEANS FOR |
| | SEC'S AND FEEDERS COMING INTO THE |
| | BUILDING SHALL BE GROUPED. |
| | |
| | 10) NOTE: PLEASE PROVIDE PROPER LEGAL |
| | DOCUMENTATION THAT THIS GENERATOR ECT IS |
| | BEING PERMITTED ON THIS PROPERTY BY THE |
| | PROPERTY OWNER. |
| | PLEASE SEE THIS GEN SEEMS TO BE ONLY FOR |
| | ONE TENANT SPACEIN THE BUIDLING. |
| | |
| | 11) NOTE: PLEASE SEE ALL PLANS, DESIGNS |
| | AND LOAD CALULATIONS SHALL CONTAIN A |
| | STATEMENT" DRAWN BY: PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPSOSIBLE FOR |
| | SAID PLANS AND DESIGNS. |
| | FBC 106.1.2 |
| | |
| | |
| | ** UNABLE TO DO A COMPLETE REVIEW AT |
| | THIS TIME AS THERE ARE SOME MISSING |
| | ITEMS NEEDED. |
| | PLEASE BE SURE TO GO OVER PLANS AND |
| | RISER BEFORE RESUBMITTING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |