| Date |
Text |
| 2006-11-22 13:16:44 | ***** UNSAT 2ND REVIEW ******* |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW AND |
| | SOME NEW NOTES BASED ON NEW PLANS SUBMITTED ARE IN NEED |
| | OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE MISSING FIRM LICENSE NUMBER FROM |
| | THE TITLE BLOCKS AS REQUIRED PER FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002 AND FLORIDA STATUTES 471.023. |
| | PLEASE SEE THIS IS ALSO KNOWN AS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER OR THE ENGINEERING BUSINESS |
| | LICENSE #. |
| | |
| | 2) NOTE: PLEASE SHOW MINIMUM EGRESS LIGHTING CONTROL |
| | AND FIXTURE(S) REQUIRED AT EGRESS DOOR TO REAR OF |
| | DWELLING. |
| | 210.70, LS101 7.8 |
| | |
| | 3) NOTE: PLEASE SEE MISSING THE REQUIRED DISCONNECTS |
| | FOR THE AHU AND THE WH UNIT. 422.31, 440.11. |
| | PLEASE INDICATE ON PLANS. |
| | |
| | 4) NOTE: PLEASE SEE AS NEW PANEL SCHEDULE IS PROVIDED, |
| | PLEASE CLARIFY THE PANEL BEING SHOWN AS 150A BUS, AND |
| | 150A MLO, YET THE LOAD CALCULATIONS MENTIONS A 125A |
| | BREAKER FOR MAIN. IS THIS A MAIN DISCONNECT AT THE |
| | SERVICE LOCATION WHICH FEEDS THIS PANEL? |
| | PLEASE SHOW THE LOCATION OF THE PANEL AS THIS IS NOT |
| | SHOWN ON PLANS. |
| | PLEASE VERIFY AND SHOW. 110.26, 408.7, 240.24 |
| | FBC106.1.2. |
| | |
| | 5) NOTE: PLEASE SEE PLANS SHALL BE SPECIFIC IN DESIGN |
| | FOR THE CURRENT CODE ADOPTED BY THE STATE OF FLORIDA. |
| | PLEASE SEE WE ARE UNDER THE 2004 FBC, 2002 NFPA-70, |
| | 2002 NFPA-72, THESE ARE REQUIRED FOR ELECTRICAL AT A |
| | MIN. |
| | MAY NOT STATE THE "LATEST" AS THOSE CODES WHICH ARE OUT |
| | ARE NOT YET ADOPTED. |
| | |
| | 6) NOTE: PLEASE SEE NOC SUBMITTED IS NOT COMPLETE. |
| | PLEASE SEE FS 713.13 AS A RECORDED NOC IS REQUIRED |
| | BEFORE PICKING UP PERMIT. THIS IS NOT REQUIRED WHEN |
| | SUBMITTING PLANS, HOWEVER MAY BE. |
| | PLEASE SEE THE NOC IN PACKAGE IS NOT RECORDED AS |
| | REQUIRED. |
| | PLEASE SEE WE HAVE ATTACHED A SIMPLE ONE PAGE NOC WHICH |
| | SHOULD BE USED IN LIEU OF THE TWO PAGES SUBMITTED. |
| | PLEASE SEE FS 117.05 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |