| 2006-08-06 00:00:00 | ***** UNSAT ******* |
| | |
| | 1) NOTE: PLEASE SUBMIT AND SHOW NEW |
| | ELECTRICAL FOR NEW HABITABLE ROOMS PER |
| | 210.52 |
| | |
| | 2) NOTE: PLEASE SEE PLANS MENTIONS A NEW |
| | BEDRM, THEN SCRATCHED OUT AND MENTIONS |
| | OFFICE. PLEASE KNOW IF THIS IS AN |
| | ADAPTABLE SLEEPING ROOM A SD MAY BE |
| | REQUIRED. IN EITHER CASE PLEASE SEE 2004 |
| | R313. PLEASE VERIFY ALL LOCATIONS FOR |
| | SD'S BEING BROUGHT UP TO THE CURRNT CODE |
| | OR SHOW EXISTING WHICH MEETS CURRENT |
| | CODE. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | ** PLEASE SEE THAT ALL SD'S ARE REQUIRED |
| | TO BE WIRED IN LINE ETC. |
| | |
| | 3) NOTE: PLEASE SHOW MIN EGRESS LT |
| | CONTROL AND FIXTIRE(S) REQUIRED. |
| | 210.70, LS101 7.8 |
| | |
| | 4)NOTE: PLEASE SPECIFY THE NEW DEDICATED |
| | DINING 20A CIRCUIT(S). PLEASE SEE |
| | 210.52B1,210.11C1,220.16 |
| | |
| | 5) NOTE: PLEASE INCLUDE A PANEL SCHEDULE |
| | FOR NEW CIRCUITS BEING ADDED. |
| | 408.4, FBC 106.1.2 |
| | |
| | 6) NOTE : PLEASE SEE PLANS SHALL BE |
| | SPECIFIC IN DESIGN FOR THE CURRENT CODE |
| | ADOPTED BY THE STATE OF FLORIDA. |
| | PLEASE SEE WE ARE UNDER 2004 FBC, 2002 |
| | NFPA-70 , 2002 NFPA-72, THESE ARE |
| | REQUIRED FOR ELECTRICAL AT A MIN. |
| | MAY NOT STATE THE "LATEST" AS THOSE |
| | CODES WHICH ARE OUT ARE NOT YET ADOPTED. |
| | |
| | 7) NOTE: PLEASE SEE THAT WHEN PLANS ARE |
| | NOT REQUIRED TO BE DONE BY AN ARCHITECT |
| | OR ENGINEER , THE PERSON RESPONSIBLE FOR |
| | PLANS AND DESIGN SHALL CLEARLY STATE |
| | DRAWN BY: PRINTED NAME AND SIGNATURE. |
| | FBC106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE NOC SUBMITTED IS NOT |
| | COMPLETE WITH ALL INFORMATION AS |
| | REQUIRED ON A NOTICE OF COMMENCMENT |
| | WHICH IS REQUIRED TO BE RECORDED AND |
| | SUBMITTED BEFORE PICKING UP PERMIT. |
| | PLEASE SEE FS 713.13 FOR ALL INFORMATION |
| | REQUIRED AND PLEASE BE SURE THIS IS |
| | NOTARIZED AS REQUIRED. PLEASE SEE FS |
| | 117.05 FOR REQUIREMENTS FOR THE NOTARY. |
| | |
| | ** PLEASE KNOW, PLANS SHALL BE SPECIFIC |
| | IN DESIGN AND MAY NOT STATE ALL PER CODE |
| | IN LEIU OF DEATAILS REQUIRED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |