Plan Review Notes
Plan Review Notes For Permit 06071240
Permit Number 06071240
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-08-16 00:00:00***DENIED***
  
 1) PLEASE SHOW THE LOCATION OF ALL
 REQUIRED SMOKE DETECTORS, NEW OR
 EXISTING.
  
 2) PLEASE CLARIFY THE USE OF THE ROOM
 THAT IS NOW IDENTIFIED AS A DEN.
  
 3) NEW SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF (3)' FROM AC
 DIFFUSERS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722