| 2007-01-22 18:24:10 | BUILDING PLAN REVIEW |
| | PERMIT: 06071230 |
| | ADD: 205 N.DIXIE HWY |
| | CONT: H.A. CONTRACTING CORP. |
| | TEL: (305)591-9212 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)WPB AMENDMENTS 108.3*THE VALUE IS TO LOW. IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| | VALUATION OF THE BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHINICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| | SHALL BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| | TO INCLUED STRUCTURAL ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISH, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COST, OVERHEAD AND PROFIT: EXCLUDING LAND. |
| | OUR VALUATION REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND |
| | MEANS COST ANALYSIS SERVICES. |
| | |
| | 3)THE IT EQUIP ROOM SHALL BE DESIGN TO NFPA. 75 CH. |
| | 5.1. ALL WALL SHALL BE AT LEAST ONE HOUR RATED. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| 2007-01-05 18:30:59 | NEW RATED ROOM,, NOT ONLY DEMO. |