| 2006-08-05 00:00:00 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE PROVIDE MORE DETAIL ON | | | ELECTRICAL PLANS. PLEASE SEE PLANS SHOWS | | | ON PANEL BEING MOVED, YET SHOWS THREE | | | PANELS? | | | PLEASE PROVIDE CIRCUITING AND CORRELATE | | | WITH MINIMUM PANEL SCHEDULE(S) TO BE | | | SUBMITTED. | | | PLEASE SEE NEC 645 AND NFPA-75 FOR | | | REQUIREMENTS OF IT ROOM. | | | PLEASE SEE MISSING DISCONNECTING MEANS, | | | GROUNDING SHUT OFF'S, FOR A/C EQUIPMENT | | | AND ALL ELECTRICAL. | | | IF A/C SYSTEM ARE DUCTED IN, PLEASE BE | | | SURE TO PROVIDE FIRE DAMPERS AS | | | REQUIRED.(MAY BE PART OF MECH REVIEW) | | | PLEASE SEE BLDG REVIEW COMMENTS FOR MIN | | | RATINGS OF ALL WALLS TO BE CLARIFIED. | | | | | | ** PLANS ARE NOT CLEAR AT THIS TIME FOR | | | ALL MIN REQUIRMENTS PER ABOVE. | | | | | | 408.4,240.4,240.24,408.7,110.26 ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|