| Plan Review Notes For Permit 06071222 |
| Permit Number |
06071222 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-07 00:00:00 | | | | | | | DENIED | | | | | | 1) PROVIDE BLDG CONSTRUCTION TYPE AND | | | OCCUPANCY ON DRAWINGS | | | | | | 2) CORRECT THE FOLLOWING ON A5.O | | | | | | A) PROVIDE NOTE THAT ALL WOOD FURRING TO | | | BE FIRE RETARDANT OR REFFER TO NOTE #33 | | | IN GENERAL NOTES | | | B) DETAIL 02 & 03 REFFER TO WOOD TRIM IN | | | DETAIL 06/A5.0 (STONE BASE DETAIL) | | | | | | 3) TITLE BLOCK ADDRESS SHALL GIVE | | | LOCATION OF WORK (9TH FLOOR LOBBY) | | | | | | 4) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|