| Plan Review Notes For Permit 06071194 |
| Permit Number |
06071194 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-07 16:16:48 | *** DENIED *** | | | 1) 10" RETURN AIR TRANSFER DUCT TO EXISTING BEDROOM | | | NEEDS TO BE 12" (SEE YELLOW HIGH LIGHT ON MECHANICAL | | | PLAN), SEE 2004 FBC/R 1602.4 (A). | | | | | | 2) 12" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE | | | NEEDS TO BE 14", SEE 2004 FBC/R M1602.4 (A) AND (C) | | | EXCEPT. | | | | | | *** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE | | | ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|