Plan Review Notes
Plan Review Notes For Permit 06071194
Permit Number 06071194
Review Stop M
Sequence Number 3
Notes
Date Text
2007-03-07 16:16:48*** DENIED ***
 1) 10" RETURN AIR TRANSFER DUCT TO EXISTING BEDROOM
 NEEDS TO BE 12" (SEE YELLOW HIGH LIGHT ON MECHANICAL
 PLAN), SEE 2004 FBC/R 1602.4 (A).
  
 2) 12" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE
 NEEDS TO BE 14", SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT.
  
 *** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.