| 2007-04-03 15:56:38 | |
| | DENIED |
| | |
| | 1)SITE PLAN MUST SHOW DRAINAGE IN COMPLIANCE WITH THE |
| | REQUIREMENTS OF R403.1 WATER MUST DRAIN AWAY FROM |
| | BUILDING AND PROPERTY LINE SO THAT IT DOES NOT FLOW |
| | ONTO ADJACENT PROPERTY. |
| | |
| | 2)SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION THAT |
| | HAVEE BEEN REVIEWED AND APPROVED BY THE |
| | DESIGNER OF RECORD. THESE MUST BE ORIGINAL SIGNED AND |
| | SEAL BY THE DESIGN ENGINEER FROM THE TRUSS |
| | MANUFACTURER. |
| | |
| | 3)THE FOLLOWING ARE PROBLEMS WITH THE PRODUCT |
| | APPROVALS. |
| | A) YOU HAVE SUBMITTED THE CORRECT FLORIDA COVER SHEET |
| | FOR THE PGT SINGLE HUNG WINDOWS BUT THERE ARE SEVERAL |
| | DIFFERENT TYPES AND SOME ARE IMPACT SOME ARE NOT PLEASE |
| | CHOOSE THE MODEL OF WINDOW YOU PLAN TO USE. ALSO ONCE |
| | CHOSEN SUBMIT THE INSTRUCTIONS WHICH IN THIS CASE ARE |
| | THE MIAMI-DADE NOA (SEE HI-LITE ON PAGE 3 OF PRODUCT |
| | APPROVAL) |
| | B) THE FLORIDA COVER SHEET AND THE MIAMI-DADE NOA FOR |
| | THE GAF SHINGLES ARE OLD AND THE REVISED PRODUCT |
| | APPROVALS ARE REQUIRED. |
| | C) THERE ARE PRODUCT APPROVALS FOR MULLIONS AND THE |
| | DRAWINGS DO NOT SHOW A WINDOW SYSTEM WHERE THEY WOULD |
| | BE USED. IF THEY ARE TO BE USED CHANGE DRAWING TO SHOW |
| | WHERE IF NOT REMOVE FROM PACKAGE. |
| | D) THE PRODUCT APPROVALS FOR THE JELD WEN DOORS HAVE 3 |
| | SEPARATE APPROVALS STEEL DOORS, STEEL DOORS WITH SIDE |
| | LITES AND STEEL FRENCH DOORS WITH GLASS, ONLY SUBMIT |
| | THE NOA'S FOR THE TYPE OF DOOR THAT WILL BE USED. |
| | E) THE POMA STORM PANELS ARE OK AS SUBMITTED BUT ARE |
| | CLOSE TO EXPIRATION SEE DATE 4/18/07 IF THE PERMIT |
| | APPLICATION IS SUBMITTED AFTER THIS DATE REVISED NOA'S |
| | WILL BE REQUIRED. |
| | 4)ALL PRODUCT APPROVALS SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL. |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |