| 2006-12-22 16:24:29 | *** DENIED *** |
| | 1) RETURN AIR TRANSFER DUCTS TO THE THREE EXISTING |
| | BEDROOMS DOES NOT GO TO A COMMON AREA SO IT MAY RETURN |
| | TO THE AIR HANDLER UNIT, ALSO WHEN CORRECTING PLEASE |
| | CHECK AS THE 9" RETURN AIR TRANSFER DUCT FROM THE TWO |
| | GRILLS MAY NOT BE LARGE ENOUGH. |
| | |
| | 2) THE RETURN AIR TRANSFER DUCT FROM THE MASTER SUITE |
| | TO THE NEW FAMILY ROOM IS TO SMALL. BALANCED RETURN AIR |
| | MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 3) PLEASE SHOW A/C EQUIPMENT LISTING ON MECHANICAL |
| | PLANS. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |