2006-12-22 16:24:29*** DENIED ***
 1) RETURN AIR TRANSFER DUCTS TO THE THREE EXISTING
 BEDROOMS DOES NOT GO TO A COMMON AREA SO IT MAY RETURN
 TO THE AIR HANDLER UNIT, ALSO WHEN CORRECTING PLEASE
 CHECK AS THE 9" RETURN AIR TRANSFER DUCT FROM THE TWO
 GRILLS MAY NOT BE LARGE ENOUGH.
  
 2) THE RETURN AIR TRANSFER DUCT FROM THE MASTER SUITE
 TO THE NEW FAMILY ROOM IS TO SMALL. BALANCED RETURN AIR
 MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 3) PLEASE SHOW A/C EQUIPMENT LISTING ON MECHANICAL
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;