| Plan Review Notes For Permit 06071194 |
| Permit Number |
06071194 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-22 14:31:19 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} AN EQUIPMENT GROUNDSIZED PER 250.122 (#6) MUST BE | | | RUN WITH THE FEEDER FROM THE DISCONNECT TO THE PANEL. | | | | | | 2} THE NOTE BY THE PANEL INDICATES IT' LOCATED IN THE | | | GARAGE, BUT IT'S SHOWN IN THE LAUNDRY ROOM ON THE PLAN. | | | PLEASE CLARIFY. | | | | | | 3} THE ICE MAKER AND MICROWAVE IN THE LOAD CALCULATION | | | DO NOT APPEAR ON THE PANEL SCHEDULE. | | | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.THIS | | | COMMENT WAS ON THE PREVIOUS REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|