Plan Review Notes
Plan Review Notes For Permit 06071194
Permit Number 06071194
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-22 14:31:19 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} AN EQUIPMENT GROUNDSIZED PER 250.122 (#6) MUST BE
 RUN WITH THE FEEDER FROM THE DISCONNECT TO THE PANEL.
  
 2} THE NOTE BY THE PANEL INDICATES IT' LOCATED IN THE
 GARAGE, BUT IT'S SHOWN IN THE LAUNDRY ROOM ON THE PLAN.
 PLEASE CLARIFY.
  
 3} THE ICE MAKER AND MICROWAVE IN THE LOAD CALCULATION
 DO NOT APPEAR ON THE PANEL SCHEDULE.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.THIS
 COMMENT WAS ON THE PREVIOUS REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.