2006-08-02 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} DUE TO THE METER LOCATION, A
 DISCONNECT IS REQUIRED PER 225.32.
 INDICATE LOCATION ON PLAN.
  
 2} THE RISER INDICATES A 200 AMP MAIN
 PANEL AND THE PANEL SCHEDULE INDICATES A
 150 AMP PANEL. INDICATE ACTUAL OR
 PROPOSED CONDITIONS.
  
 3} THE EQUIPMENT GROUND BETWEEN THE
 METER AND THE DISCONNECT ON THE RISER
 DIAGRAM CREATES A PARALLEL PATH TO
 GROUND WITH THE NEUTRAL AND MUST BE
 REMOVED. AN ISOLATED NEUTRAL AND
 EQUIPMENT GROUND ARE TO BE RAN FROM THE
 FIRST MEANS OF DISCONNECT. 250.6.
  
 4} CIRCUITS 2,4 AND 9,11 HAVE WIRE AND
 OVERCURRENT PROTECTION UNDERSIZED FOR
 THE LOAD SERVED. 310.16.
  
 5} NOTE #6 SHOULD INCLUDE FOOTER STEEL,
 SINCE IT IS AVAILABLE, PER 250.(A)(3).
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO
 SAME PER 106.3.4.2.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  