| Notes |
| Date |
Text |
| 2006-08-02 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} DUE TO THE METER LOCATION, A | | | DISCONNECT IS REQUIRED PER 225.32. | | | INDICATE LOCATION ON PLAN. | | | | | | 2} THE RISER INDICATES A 200 AMP MAIN | | | PANEL AND THE PANEL SCHEDULE INDICATES A | | | 150 AMP PANEL. INDICATE ACTUAL OR | | | PROPOSED CONDITIONS. | | | | | | 3} THE EQUIPMENT GROUND BETWEEN THE | | | METER AND THE DISCONNECT ON THE RISER | | | DIAGRAM CREATES A PARALLEL PATH TO | | | GROUND WITH THE NEUTRAL AND MUST BE | | | REMOVED. AN ISOLATED NEUTRAL AND | | | EQUIPMENT GROUND ARE TO BE RAN FROM THE | | | FIRST MEANS OF DISCONNECT. 250.6. | | | | | | 4} CIRCUITS 2,4 AND 9,11 HAVE WIRE AND | | | OVERCURRENT PROTECTION UNDERSIZED FOR | | | THE LOAD SERVED. 310.16. | | | | | | 5} NOTE #6 SHOULD INCLUDE FOOTER STEEL, | | | SINCE IT IS AVAILABLE, PER 250.(A)(3). | | | | | | THE PERSON TAKING RESPONSIBILITY FOR THE | | | DESIGN MUST PRINT AND SIGN THEIR NAME TO | | | SAME PER 106.3.4.2. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | |
|