| Date |
Text |
| 2006-08-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 EXISTING BLDG. |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. REMODEL IS A CHANGE OF OCCUPANCY. AS |
| | SUCH ALL PROVISIONS SHALL BE COMPLIED |
| | WITH FOR THE NEW OCCUPANCY. SECTION |
| | 810.1. |
| | |
| | 2. PLANS SHALL BE DESIGNED BY A DESIGN |
| | PROFESSIONAL. FS481.229(C) AND SHALL BE |
| | SIGNED, SEALED, DATED AND HAVE A TITLE |
| | BLOCK WITH ALL REQUIRED INFORMATION. FAC |
| | 61G1-23.004 & FS481.2055. |
| | |
| | 3. PER TABLE 403.1 A DRINKING FOUNTAIN |
| | IS REQUIRED. PLEASE SHOW CONNECTION TO |
| | SANITARY RISER DIAGRAM AND THE WATER |
| | RISER DIAGRAM THAT REFLECTS THE FLOOR |
| | PLAN. SECTION 106.3.5.1.3. SHOW ALL PIPE |
| | SIZES, TRAPS, VENTS, ON SANT. AND ALL |
| | PIPE SIZES, VALVES, ETC. ON WATER. - |
| | SUBMIT A DETAIL FOR THE DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH 11-4.15 |
| | AND ALL SUBSECTIONS AS WELL AS |
| | 11-4..3(10)(A) PROVISIONS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 4. GENERAL PROJECT NOTES INDICATE AN |
| | EXISTING RESIDENCE. AS A RESIDENCE, A |
| | KITCHEN SINK IS REQUIRED. PLEASE |
| | INDICATE THE LOCATION OF THE SINK AS IT |
| | IS NOT SHOWN ON THE EXISTING FLOOR PLAN. |
| | IF THE SINK IS TO BE RETAINED, IT SHALL |
| | COMPLY WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. ALSO REQUIRED IN A |
| | RESIDENCE IS A WASH MACHINE HOOK UP FOR |
| | WATER AND SANIT. DWV. THIS IS NOT SHOWN |
| | ON THE EXISTING FLOOR PLAN. PLEASE |
| | SUBMIT A FLOOR PLAN THAT SHOWS THE |
| | EXISTING FLOOR PLAN WITH ALL FIXTURES, |
| | EXISTING BEDROOMS, EXISTING KITCHEN ETC. |
| | SECTION 106.1.1. |
| | |
| | 5. IF TOILET ROOMS ARE PROVIDED, THEN |
| | EACH PUBLIC AND COMMON USE TOILET ROOM |
| | SHALL COMPLY WITH SECTION 11-4.22. |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| | SECTIONS 11-4.16, 11-4.19, & 11-4.22 |
| | WITH ALL SUBSECTIONS. |
| | |
| | 6. AN RPZV BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. SECTION |
| | 608. INDICATE ON PLANS. |
| | |
| | 7. THERMAL EXPANSION CONTROL IS REQUIRED |
| | PER SECTION 607.3.2. |
| | |
| | 8. INDICATE THE SQUARE FOOTAGE OF THE |
| | FLOOR PLAN TO CHECK MINIMUM FACILITIES |
| | REQUIRED PER TABLES 1004.1.2 & 403.1. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |