| Plan Review Notes For Permit 06071193 |
| Permit Number |
06071193 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-07 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE NOTE THAT TWO DIFFERENT | | | ADDRESSES ARE SHOWN ON PERMIT | | | APPLICATION AND PLANS. PLEASE CORRELATE | | | AND MAKE CORRECTIONS. | | | | | | 2) ADDRESS IS REQUIRED ON BUIDING AND | | | SHALL BE MINIMUM OF 6" IN HEIGHT AND | | | CONTRASTING TO THE BACKGROUND FOR | | | COMMERCIAL BUILDINGS. | | | | | | 3) EXIT SIGNS WILL BE REQUIRED. PLEASE | | | SHOW ON PLANS. | | | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED AT EACH | | | LEVEL NOT TO EXCEED 75' TRAVEL DISTANCE | | | REQUIREMENT. | | | | | | 5) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 6) NOTES ON SITE PLAN REFERENCE SLEEPING | | | ROOMS. PLEASE REMOVE INFORMATION THAT IS | | | NOT PERTINENT TO THIS PROJECT AS IT | | | APPLIES TO THE CHANGE OF OCCUPANCY. | | | | | | 7) CONSRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|