| 2006-08-10 00:00:00 | ****UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE THAT PLANS REFLECT |
| | ALL OF THE FOLLOWING CODES AT A MINIMUM. |
| | 2004 FBC, 2002 NFPA-70, 2002 NFPA-72, |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SUBMIT PLANS WHICH ARE |
| | DONE BY A MINIMUM OF AN ARCHITECT, |
| | SIGNED, DATED AND SEALED BY SAID |
| | PROFESSIONAL. PLEASE ALSO BE SURE ALL |
| | TITLE BLOCK INFORMATION IS ON SAID |
| | PLANS. |
| | FS 481.229, 481.221, 471.025 |
| | FAC 61G15-23.002, 61G1-16.004. |
| | |
| | 3) NOTE: PLEASE SSUBMIT ELECTRICAL PLANS |
| | IN COMPLIANCE WITH THE 2002 NEC. |
| | PLEASE SEE PLANS FOR SERVICE DO NOT |
| | CORRELATE, PLEASE SEE LOAD CALCULATIONS |
| | ARE NOT CORRECT AND THERE ARE MANY ITEMS |
| | MISSING. |
| | PLEASE SEE 2002 NEC, |
| | 220.3,220.10,220.11,220.13, ETC, 215.5, |
| | 215.3, 230.42, ETC |
| | |
| | 4) NOTE: PLEASE SEE MISSING EXIT AND |
| | EMERGENCY LTS REQUIRED. |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS. |
| | PLEASE SEE NFPA-101 2003 7.8.1.3, |
| | 7.9.2.2 AS THE MIN FT CANDLES REQUIRE |
| | UNDER NORMAL LIGHTING LEVELS ON THE |
| | STAIRS AND THE MIN LEVELS REQUIRED UNDER |
| | EM PWR(BATTERY BACK UP). |
| | PLEASE ALSO SEE ANY OPENING LEADING TO |
| | DIRECT GRADE LEVEL ACCESS SHALL ALSO |
| | CONTAIN CONTROL FOR EGRESS LTS. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH AMY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| 2006-07-23 00:00:00 | *** THIS IS NOT RESIDENTIAL. THIS IS A |
| | CHANGE IN OCCUPANCY AND PLANS ARE BEING |
| | ROUTED BACK TOINCOMING. |
| | PERMIT TYPE HAS BEEN CHANGED IN COMPUTER |
| | AND FEES ADDED FOR FIRE REVIEW. |