Plan Review Notes
Plan Review Notes For Permit 06071187
Permit Number 06071187
Review Stop M
Sequence Number 2
Notes
Date Text
2006-08-22 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE TO MUCH
 ELECTRICAL PLAN DETAIL ON THEM AND THE
 DUCT LAY-OUT IS FADED AND DIFFICULT TO
 READ, PLEASE SUBMIT A MECHANICAL PLAN
 NOT A ELECTRICAL PLAN. AS NOTED IN LAST
 REVIEW 7-26-06. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. PER 2004
 FBC 106.1.1 .
  
 2) AS NOTED IN LAST REVIEW 7-26-06. A/C
 DUCT LAY-OUT ON FIRST FLOOR IS NOT
 DESIGNED PROPERLY. WHAT TYPE OF DUCTS
 ARE BEING USED? ROUND METAL, IF SO SHOW
 ALL TRANSITIONS AND SIZE CHANGES.
 RECTANGULAR, IF SO SHOW DUCT DIMENSIONS
 12"X ?" . OR FLEX DUCTS, IF SO SHOW ALL
 MIXING BOXES.
  
 3) NEED TO SHOW THE CFM'S AT ALL SUPPLY
 AIR GRILLS.
  
 4) ONE 12" SUPPLY AIR DUCT LEAVING AHU
 #1 IS NOT ENOUGH, PLEASE CORRECT OR
 SUBMIT A MANUAL D CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R
 M1601.1 AND FBC 13-610.1.ABC.1 .
  
 5) AND AGAIN, CONSTRUCTION DOCUMENTS
 (PLANS) SHALL BE OF SUFFICIENT CLARITY.
 PER 2004 FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.