Plan Review Notes
Plan Review Notes For Permit 06071187
Permit Number 06071187
Review Stop M
Sequence Number 1
Notes
Date Text
2006-07-26 00:00:00*** DENIED ***
 1) MECHANICAL PLAN DUCT LAY-OUT AND
 EQUIPMENT LISTING IS FADED AND DIFFICULT
 TO READ. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY. PER 2004 FBC
 106.1.1 .
  
 2) PLANS SHOW TWO DIFFERENT A/C
 EQUIPMENT LISTINGS, PLEASE CORRECT. ALSO
 HAVE EQUIPMENT LISTING SHOW HEATER
 SIZE(KW), TOTAL COOLING BTU'S, AND
 SENSIBLE BTU'S.
  
 3) SUPPLY AIR DUCT AND GRILL TO SECOND
 FLOOR BATHROOM NEEDS TO BE SIZED.
  
 4) SECOND FLOOR BATHROOM AND MASTER
 BATHROOM WATER CLOSET NEED EXHAUST FANS,
 PER 2004 FBC/R M1506 .
  
 5) RETURN AIR DUCT IN MASTER BEDROOM
 NEEDS TO BE 12", PER 2004 FBC/R M1602.4
  
 6) A/C DUCT LAY-OUT ON FIRST FLOOR IS
 NOT DESIGNED PROPERLY PLEASE CORRECT.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 7) PROVIED RETURN AIR FOR FIRST FLOOR
 AIR HANDLER.
  
 8) MANUAL J CAALCULATIONS ARE ONLY
 CALLING FOR ONE A/C SYSTEM, PLANS ARE
 CALLING FOR TWO A/C SYSTEMS, THE TWO
 MUST COINCIDE, PLEASE CORRECT.
  
 9) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 10) ENERGY CALCULATIONS NEED TO BE
 SIGNED BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 11) MECHANICAL PLANS HAVE AN ENGINEER'S
 NAME IN THE TITLE BLOCK, THEREFORE
 REQUIRE HIS SEAL AND SIGNATURE, PER FAC
 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.