Plan Review Notes
Plan Review Notes For Permit 06071166
Permit Number 06071166
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-11 00:00:00**** UNSAT 3RD REVIEW ******
  
 1) NOTE: PLEASE SEE COMMENTS FROM TWO
 PREVIOUS REVIEWS.
 PLEASE SEE THE SPECS ON THE HEAT PUMP
 STILL DO NOT INDICATE WHICH ONE IS BEING
 USED/PROPOSED AND NONE OF THE UNITS ON
 THE SPECS SUBMITTED CORRELATE WITH THE
 LOAD CALCULATIONS SUBMITTED.??
 THE LOAD CALCULATIONS DONE BY THE
 ELECTRICAL CONTRACTOR ARE OK, HOWEVER
 THEY DO NOT CORRELATE.
  
 2) NOTE: PLEASE PREVIOUS REVIEW WHICH
 REQUESTED ALL "EXISTING/OLD/VOIDED"
 SHEETS TO BE COMPLETELY REMOVED FROM
 SETS, AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SEE THE OLD LOAD CALCULATIONS ARE
 STILL IN SETS.
 THIS WAS NOT DONE.
 PLEASE ALSO SEE THAT TWO COPIES OF ALL
 PLANS/DRAWINGS ETC ARE REQUIRED AT A
 MINIMUM. PLEASE SEE ONLY ONE COPY OF THE
 REVISED PANEL SCHEDULE/LOAD CALCULATIONS
 WAS SUBMITTED. (UP TO 3 SETS MAY BE
 SUBMITTED).
 FBC 106.1.2, 106.1, ADMINSECT AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  