Plan Review Notes
Plan Review Notes For Permit 06071166
Permit Number 06071166
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-28 00:00:00****** UNSAT ******
  
 1) NOTE: PLEASE PROVIDE INFORMATION FOR
 POOL PUMP AND HEAT PUMP IF THE LOADS
 SHOWN ARE ALREADY FIGURED AT 125% FOR
 CONTINUOUS LOADS.
 215.3,230.42 ETC.
  
 2) NOTE: PLEASE SEE WIRING DIAGRAM SHOWS
 A NEW POOL PANEL, PLEASE LIST THE OCP
 FEEDING NEW PANEL ALONG WITH THE SIZE OF
 PANEL.
 PLEASE COMPLETEA POOL SUB PANEL
 SCHEDULE FOR NEW BRANCH CIRCUITS, OCP
 AND WIRES SIZES. THIS MAY BE DONE BY THE
 ELECTRICAL CONTRACTOR AND ATTACHED LIKE
 THE LOAD CALCULATIONS ARE.
 240.4,310.16,408.4
  
 3) NOTE: PLEASE SEE WIRING DIAGRAM FOR
 POOL HEATER DOES NOT INCLUDE ANY
 CONDUCTOR SIZES. PLEASE CORRELATE WITH
 THE ELECTRICAL PANEL SCHEDULE AND SHOW
 ON PLANS.
 106.1.2 FBC ADMIN SECT, 240.4,310.16
 ETC.
  
 4) NOTE: PLEASE BES URE THE ADDTIONAL
 SHEETS FOR LOAD CALCULATIONS AND PANEL
 SCHEDULE CONTAINS THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN/CALCS ETC.
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  