| Notes |
| Date |
Text |
| 2006-07-28 00:00:00 | ****** UNSAT ****** | | | | | | 1) NOTE: PLEASE PROVIDE INFORMATION FOR | | | POOL PUMP AND HEAT PUMP IF THE LOADS | | | SHOWN ARE ALREADY FIGURED AT 125% FOR | | | CONTINUOUS LOADS. | | | 215.3,230.42 ETC. | | | | | | 2) NOTE: PLEASE SEE WIRING DIAGRAM SHOWS | | | A NEW POOL PANEL, PLEASE LIST THE OCP | | | FEEDING NEW PANEL ALONG WITH THE SIZE OF | | | PANEL. | | | PLEASE COMPLETEA POOL SUB PANEL | | | SCHEDULE FOR NEW BRANCH CIRCUITS, OCP | | | AND WIRES SIZES. THIS MAY BE DONE BY THE | | | ELECTRICAL CONTRACTOR AND ATTACHED LIKE | | | THE LOAD CALCULATIONS ARE. | | | 240.4,310.16,408.4 | | | | | | 3) NOTE: PLEASE SEE WIRING DIAGRAM FOR | | | POOL HEATER DOES NOT INCLUDE ANY | | | CONDUCTOR SIZES. PLEASE CORRELATE WITH | | | THE ELECTRICAL PANEL SCHEDULE AND SHOW | | | ON PLANS. | | | 106.1.2 FBC ADMIN SECT, 240.4,310.16 | | | ETC. | | | | | | 4) NOTE: PLEASE BES URE THE ADDTIONAL | | | SHEETS FOR LOAD CALCULATIONS AND PANEL | | | SCHEDULE CONTAINS THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | PLANS/DESIGN/CALCS ETC. | | | FBC 106.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|