| 2006-11-22 09:53:19 | *** UNSAT 3RD REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT ELECTRICAL FOR MINIMUM CODE |
| | COMPLIANCE. PLEASE SEE THE MIN SIZE OF THE CONDUCTORS |
| | SHALL BE BASED ON THE NEW CIRCUITS BEING PROVIDED. |
| | PLEASE SEE 240.4,310.16, 220.18, 220.11C1, 220.16. |
| | DRYER CAN NOT BE 14/3, NOR CAN THE WASHER CIRCUIT. |
| | PLEASE SEE BUNDLING OF THESENMC (ROMEX'S) IN ONE |
| | METAL CONDUIT ON THE OUTSIDE OF THE BUILDING IS ALSO |
| | NOT PERMITTED. |
| | PLEASE SEE TABLES IN 310.16 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | SMOKE ALARM DEVICES REQUIRED PER FBC R313. PLEASE SHOW |
| | DEVICES IN EXISTING DWELLING EITHER MEETING THE CURRENT |
| | REQUIREMENTS OF NFPA-72 11.5.1.1 OR NEW TO BE |
| | INSTALLED. |
| | (ALL ARE REQUIRED TO BE WIRED INLINE). |
| | |
| | 3) NOTE: PLEASE SEE NEW ROOM RECEPTACLE SPACING SHALL |
| | MEET 210.52. |
| | |
| | 4) NOTE: PLEASE SEE MISSING EGRESS LIGHTING CONTROL |
| | FROM ROOM TO OUTSIDE AS REQUIRED PER 210.70 AND LS 101 |
| | 7.8 |
| | |
| | 5) NOTE: PLEASE CLARIFY IF THIS IS GOING TO BE A NEW |
| | LOCATION FOR LAUNDRY ROOM OR ARE THE EXISTING |
| | FACILITIES BEING RELOCATED? |
| | PLEASE SHOW SIZE OF PANEL, THE SIZE?S OF THE BREAKERS |
| | FEEDING THE NEW CIRCUITS. |
| | 240.4,310.16, 408.4. |
| | |
| | 6) NOTE: PLEASE BE SURE ALL SUBMITTED DRAWING DONE |
| | CONTAIN A PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLANS AND DESIGN. |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | *IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE |
| | NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO |
| | NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |