Plan Review Notes
Plan Review Notes For Permit 06071139
Permit Number 06071139
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-15 00:00:00 
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION. NEW LOCATION 2300 N.JOG RD
 (NORTH OF OKEECHOBEE BLVD)SUITE#2W01-
 2W14).
  
 3) ACCORDING TO THE SIMPSON STRONG-TIE
 CATALOG, THE WAY THE LS50 AND LS30
 CONNECTORS ARE SHOWN ON THE DRAWINGS, IS
 NOT HOW THEY WERE INTENDED TO BE USED.
 PLEASE SEE THE SIMPSON STRONG-TIE
 CATALOG FOR MORE INFORMATION AND
 INDICATE THE CORRECT CONNECTOR/STRAP FOR
 THE UPLIFT RESISTANCE.
  
 4) EXPLAIN WHY EIGHT PIECES OF PT 2X8
 ARE STACKED ON EACH OTHER TO BUILD UP
 THE COLUMS INSTEAD OF OTHER METHODS OF CONSTRUCTION.
 THE LIQUID NAILS WILL
 DETERIORATE OVER TIME AND THE STACKED
 PIECES WILL SHRINK AND CAUSE OTHER
 STRUCTURAL PROBLEMS IN DUE TIME. ONCE
 AGAIN THE LS50 SHOULD NOT BE USED AS A
 CONNECTOR FOR THE BEAM TIE-DOWN.
  
 5) FBC TABLE 2304.9.1 THE NAIL SPACING
 OF THE WALL AND FLOOR SHEATING SHALL BE
 6" O.C. EDGES AND INTERMEDIATE. 4" O.C.
 AT COMPONENT AND CLADDING EDGE STRIP #3.{FIG.1609.C}.
  
 6) R319.1 LOCATION REQUIRED.
 IN AREAS SUBJECT TO DECAY DAMAGE AS
 ESTABLISHED BY TABLE R301.2(1) , THE
 FOLLOWING LOCATIONS SHALL REQUIRE THE
 USE OF AN APPROVED SPECIES AND GRADE OF
 LUMBER, PRESSURE TREATED IN ACCORDANCE
 WITH AWPA C1, C2, C3, C4, C9, C15, C18,
 C22, C23, C24, C28, C31, C33, P1, P2 AND
 P3, OR DECAY -RESISTANT HEARTWOOD OF
 REDWOOD, BLACK LOCUST, OR CEDARS.
  
 7) R319.1.1 GROUND CONTACT.
 ALL WOOD IN CONTACT WITH THE GROUND AND
 THAT SUPPORTS PERMANENT STRUCTURES
 INTENDED FOR HUMAN OCCUPANCY SHALL BE
 APPROVED PRESSURE PRESERVATIVE TREATED
 WOOD SUITABLE FOR GROUND CONTACT USE,
 EXCEPT UNTREATED WOOD MAY BE USED WHERE
 ENTIRELY BELOW GROUNDWATER LEVEL OR
 CONTINUOUSLY SUBMERGED IN FRESH WATER.
  
 8) INDICATE THE CONNECTION OF THE FLOOR
 JOISTS TO THE SLEEPERS. WILL THE 30LB
 FELT BE INSTALLED AT THE TOP OR BOTTON
 OF THE SLEEPERS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  