2006-07-22 00:00:00***** UNSAT ******
  
 1) NOTE: PLANS ROUTED TO ADDRESSING
 REVIEWER AS SITE LOCATION ADDRESS NEEDS
 TO BE VERIFIED.
  
 2) NOTE: PLEASE SEE SCOPE OF WORK SHOWN
 REQUIRES THE RISER TO BE DRAWN UP AND
 DONE BY A PE PER FBC ADMIN SECT
 105.3.1.2, FS 471.003(H).
 PLEASE KNOW, ALL PLANS SHALL CONTAIN THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS AND DESIGN EVEN
 WHEN NOT DONE BY E PE OR ARCH.
 FAC 106.1.2
 PLEASE BE SURE TO CLARIFY RISER AS SHOWN
 AND PROVIDE MORE DETAIL ON LOCATION.
 PLEASE KNOW, IF ANY OF THIS WORK IS DONE
 ACCROS CITY RIGHT OF WAY, ETC, AN
 REVOCABLE PERMIT MUST FIRST BE OBTAINED
 THROUGH ENGINEERING AND CITY'S LAW DEPT.
 THIS DOES NOT APPLLYIF ALL WORK IS ON
 PRIVATE PROPERTY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  