Plan Review Notes
Plan Review Notes For Permit 06071107
Permit Number 06071107
Review Stop G
Sequence Number 2
Notes
Date Text
2006-09-18 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW ON THE
 ISOMETRIC DRAWING. (NOTE: THE FOLLOWING
 PRIVIOUS COMMENTS WERE NOT ADDRESSED)
  
 1. COMMENT #1 (UNSAT)
 NOTE: ABOVE GROUND PIPING MATERIAL IS
 STILL NOT INDICATED ON THE ISOMETRIC GAS
 RISER DIAGRAM.
  
 2. COMMENT #2 (OK)
  
 3. COMMENT #3 (UNSAT)
 BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE
 FBC-2004 FUEL GAS CODE SECS. 401.8 THRU
 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (NOTE: THIS INCLUDES THE
 EXISTING GAS SYSTEM, PLEASE SEE ATTACHED
 PERMIT INFORMATION SHEET FOR REFERENCE
 OF EXISTING SYSTEM HAVING GAS FOR
 RESUBMITTAL. THE TOTAL BTU LOAD OF
 SYSTEM NEEDS TO BE INDICATED ON THE
 DRAWING.)
  
 4. COMMENT #4 (UNSAT)
 SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (NOTE: THIS
 INCLUDES THE EXISTING GAS SYSTEM AS WELL
 AS THE PROPOSED GAS TO THE GENERATOR.
 THE GAS SYSTEM IS SIZED BY THE LONGEST
 LENGTH METHOD, THE ONLY MEASUREMENT
 INDICATED ON THE GAS ISOMETRIC IS 15'
 +/- THIS IS UNACCEPTABLE. THE GAS METER
 INDICATED ON THE SITE PLANIS INDICATED
 ON THE OTHER SIDE OF THE HOUSE AND IS
 DEFINITELY LONGER THAN 15'. PLEASE
 INDICATE THE LONGET LENGTH FROM METER TO
 THE MOST REMOTE OUTLET IN THE BUILDING
 OR SYSTEM. PLEASE CORRECT THIS FOR THE
 RESUBMITTAL.
  
 5. COMMENT #5 (OK)
  
 6. COMMENT #6 (OK)
  
 7. COMMENT #7 (OK)
  
 8. COMMENT #8 (OK)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved