| 2006-09-17 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE SEE SOME NOTE FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO REVISED |
| | PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE CORRELATE SITE/SURVEYS. |
| | PLEASE SEE THE PREVIOUS SURVEY/SITE PLAN |
| | INDICATED THE ELECTRICAL SERVICE AT ONE |
| | LOCATION AND THE NEW PLAN SHOWS THE |
| | SERVICE COMPLETELY ON THE OTHER SIDE OF |
| | THE HOUSE?? |
| | PLEASE INDICATE HOW AND WHICH ROUTE IS |
| | BEING TAKEN TO FEED SERVICE FROM GEN ON |
| | THE SITE PLANS,WHICH IS NOW ON THE |
| | OTHER SIDE OF THE DWELLING. |
| | 106.1.2 FBC |
| | |
| | 2) NOTE: PLEASE SEE SITE PLANS MENTIONS |
| | AN ATS AND INTEGRAL SUB PANEL, YET THE |
| | MANUFACTURE'S SPECS CUTSHEETS AND |
| | RISER DO NOT CORRELATE WITH THIS?? |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE PROVIDE A DISCONNECTING |
| | MEANS FOR THE FEEDERS COMING FROM THE |
| | GENERATOR GROUPED IN CLOSE PROXIMITY |
| | WITH THE EXISTING/NEW MAIN BEING |
| | PROPOSED. PLEASE KNOW ON OTHER PROJECTS |
| | BY THE SAME CONTRACTOR, THE ATS BEING |
| | USED IS THE RTSE, WHICH CONTAINS TWO |
| | MEANS OF DISCONNECT, HOWEVER THIS IS NOT |
| | WHAT HAS TO BE USED OR INSTALLED. |
| | 225.31-225.39 |
| | |
| | 4) NOTE: PLEASE CLARIFY THE LOAD ON THE |
| | HEAT STILL BEING SHOWN AT 3.8KVA.?? |
| | THE HEAT LOAD ON A DWELLING THIS SIZE IS |
| | NOT TYPICALLY 3.8KW. THIS IS ONLY NOTED, |
| | AS VERIFICATION IN FIELD WILL TAKE |
| | PLACE, AND PLANS MAY NEED TO BE REVISED. |
| | THIS IS ONLY NOTED TO VERIFY AS THE LOAD |
| | INDICATED SEEMS VERY LOW. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |