| 2006-07-28 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE KNOW, BEFORE PICKING UP |
| | THE PERMIT FOR THE GENERATOR, THE |
| | NOTICE OF COMMENCEMENT WILL BE REQUIRED |
| | TO BE RE-RECORDED AS THE NOC SUBMITTED |
| | HAS BECOME "VOID". PLEASE SEE FS |
| | 713.13(2), IF WORK HAS NOT COMMENCES |
| | WITH IN 90DAYS OF RECORDING THE NOC , |
| | THE NOC SHALL BECOME VOID. |
| | |
| | 2) NOTE: PLEASE VERIFY THE GENBEING |
| | USED,A S THE SITE PLANS CALL FOR UNIT TO |
| | BE 73DB'S AT 23 FT YET THE SPECS |
| | SUBMITTED INDICATE MUCH LOWER RATINGS. |
| | PLEASE CORRELATE. IS UNIT DIFFERENT THAN |
| | THE ONE SUBMITTED ON SPECS?? |
| | |
| | 3) NOTE: PLEASE INDICATE ON RISER THE |
| | ATS BEING SE RATED. |
| | PLEASE ALSO HIGHLIGHT THE CORRECT ATS ON |
| | SUBMITTIAL. |
| | 110.3,90.7 |
| | |
| | 4) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR AFTER THE FIRST |
| | MEANS OF DISCONNECT. |
| | 250.110,250.24B,250.122 ETC |
| | |
| | 5) NOTE: PLEASE PROVIDE THE DETAIL ON |
| | THE LOAD SHEDDING INTERLOCK RELAY BEING |
| | PROPOSED FOR "SHEDDING" OF THE HEAT |
| | STRIP. |
| | 702.5,220. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 6) NOTE: PLEASE PROVIDE ALL DIMENSIONS |
| | ON GENERATOR FROM SURROUNDING |
| | WALLS/HOUSE ETC. |
| | PLEASE KNOW, INFORMATION OPTAINED BY |
| | THIS OFFICE FROM MANUFACTURE FOR THIS |
| | TYPE OF UNIT REQUIRES A MIN OF 5' FROM |
| | ANY SURROUNDING WALLS ETC FOR |
| | VENTILATION ETC. |
| | IF DISTANCE OBTAINED IS LESS , PLEASE |
| | PROVIDE WRITTENT DOCUMENTATION FROM THE |
| | MANUFACTURE FOR THIS. |
| | "IF UNIT IS ALREADY 5', PLEASE SHOW. |
| | 110.3,90.7 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |