| 2006-11-30 08:00:54 | *** UNSAT *** |
| | |
| | *** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL |
| | NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE:NO, PLEASE SEE PLANS ARE STILL SHOWING A NEW |
| | ELECTRICAL RISER, YET PANEL SCHEDULE SHOWS AS EXISTING? |
| | PLEASE SUBMIT A NEW RISER AS PREVIOUSLY NOTED OR IF |
| | INDEED THIS IS AN EXISTING SERVICE PLEASE INDICATE |
| | THIS. THE ELECTRICAL AS SHOWN FOR NEW BACK PORCH WHICH |
| | IS REPLACING THE EXISTING BACK PORCH IS OK. |
| | |
| | PLEASE PROVIDE A COMPLETE ELECTRICAL RISER DIAGRAM FOR |
| | NEW PROPOSED 200A SERVICE UPGRADE. |
| | PLEASE SUBMIT AIC RATINGS, SEC'S, GROUNDING, CONDUITS |
| | ETC. |
| | PLEASE SHOW LOCATIONS OF PANEL(S) ON EXISTING/ NEW |
| | HOUSE OR ADDITION. |
| | PLEASE CLARIFY PANEL SCHEDULE WHICH MENTIONS "AS-BUILT" |
| | , SHOW LOCATIONS OF ALL EQUIPMENT. |
| | 110.26,240.24,215.5,250.50,110.9,310.16, |
| | 240.4 ETC |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |