2006-07-27 00:00:00****UNSAT ****
  
 1) NOTE: PLEASE PROVIDE A COMPLETE
 ELECTRICAL RISER DIAGRAM FOR NEW
 PROPOSED 200A SERVICE UPGRADE.
 PLEASE SUBMIT AIC RATINGS, SEC'S,
 GROUNDING, CONDUITS ETC.
 PLEASE SHOW LOCATIONS OF PANEL(S) ON
 EXISTING/ NEW HOUSE OR ADDITION.
 PLEASE CLARIFY PANEL SCHEDULE WHICH
 MENTIONS "AS-BUILT" , SHOW LOCATIONS OF
 ALL EQUIPMENT.
 110.26,240.24,215.5,250.50,110.9,310.16,
 240.4 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  