| 2006-10-22 12:22:24 | ****** PROVISO/ REVISION NEEDED ***** |
| | |
| | *** PLEASE SEE THE SAME NOTES FROM THE PREVIOUS THREE |
| | REVIEWS. |
| | PLEASE KNOW A "HOLD" WILL BE PLACED ON THE ELECTRICAL |
| | PERMIT NUMBER 06071025 WHICH WILL NOT PERMIT ANY |
| | INSPECTIONS TO BE SCHEDULED. |
| | PLEASE ALSO KNOW, REVISED PLANS SHALL BE SUBMITTED |
| | ADDRESSING COMMENTS BELOW WITHIN 10DAYS FROM ISSUANCE |
| | OF BUILDING PERMIT ORSAID BUILDING PERMIT WILL BE |
| | REVOKED. |
| | THIS IS THE FIRST SET OF PLANS ARE BEING SUBMITTED |
| | UNDER A NEW LICENSED ARCHITECT AS PREVIOUSLY |
| | REQUESTED. |
| | |
| | 1) NOTE: |
| | A) PLEASE SHOW AND INDICATE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED.408.4. |
| | 310.16, 240.4 FBC ADMIN SECT 106..3.5.1.2 |
| | B) PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO NOT |
| | INDICATE ALL THE MINIMUM REQUIRED CIRCUITS AS |
| | REQUIRED. |
| | C) PLEASE SEE MISSING DEDICATED BATH(S) PER 210.52D, |
| | 210.11C3 (20A, #12). |
| | D) PLEASE SEE MISSING GFI RECEPT ALONG WHAT APPEARS TO |
| | BE KITCHEN COUNTER SPACE 210.8A6, 210.52C1 |
| | E) PLEASE PLACE UNIT # ON SAID PLANS AS REQUIRED ON |
| | TITLE BLOCKS. THIS WAS HANDWRITTEN ON ELECTRICAL PLANS |
| | SUBMITTED. |
| | F) PLEASE SEE NEW SA/SD'S WILL BE REQUIRED TO BE ARC |
| | FAULT POTECTED FOR 120V SYSTEM. 210.12B |
| | F) PLEASE SEE NO OTHER PLANS WERE SUBMITTED.LAYOUT |
| | AND LOCATIONS OF CERTAIN APPLIANCES HAVE BEEN |
| | RELOCATED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. ONCE |
| | AGAIN IF THERE ARE ANY QUESTIONS, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. PLEASE KNOW , TO |
| | DATE NO CONTACT TO THIS OFFICEHAS BEEN MADE FOR ANY |
| | CODE COMPLIANCE QUESTIONS OR COMMENTS. |
| | |