 1) NOTE: PLEASE SEE 210.8A6 AS ALL
 RECEPTS SERVING KITCHEN COUNTER SPACE
 ARE REQUIRED TO BE GFI/GFI PROTECTED.
  
 2) NOTE: PLEASE SEE SCOPE OF WORK ON
 PLANS IS NOT PERMITTED IN PEN , PENCIL.
 PLEASE SEE AS PREVIOUSLY NOTED ON
 PREVIOUS REVIEW, PLANS SUBMITTED MUST BE
 DONE BY AN ARCHITECT AS REQUIRED UDNER
 FS 481.229.
 PLEASE KNOW THIS IS REQUIRED OF ALL
 PLANS EVEN IF ALREADY STAMPED BY OTHER
 TRADES.
 LEVEL OF ALTERATION SHALL BE STATED PER
 FBCEXSITING BUIDLING CODE.
 106.1.2, 106.1, 106.1.3 FBC ADMIN SECT.
  
 3) NOTE: PLEASE SEE NOTHIG SUBMITTED FOR
 NEW WATER HEATER AND NEW A/C. SAME SIZE
 UNITS, NEW OR EXISTING DISCONNECT,
 LOCATIONS? ETC
 440.11,422.31,
 PLEASE SEE THERE ARE NO LOADS INDICATED
 ON PANEL, PLEASE SEE IT IS UNCLEAR IF
 THERE IS AN INCREASE IN THE NEW UNITS.
 PLEASE ALSO COMPELTE THE LAOD
 CACULATION.
 220.31
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  