| Plan Review Notes For Permit 06071012 |
| Permit Number |
06071012 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-27 00:00:00 | ********** UNSAT ************ | | | | | | 1) NOTE: PLEASE PROVIDE AN ELECTRICAL | | | LAYOUT FOR COMPLETE SCOPE OF ELECTRICAL | | | WORK. | | | PLEASE INDICATE ALL NEW OR EXISTING GFI | | | RECEPT LOCATIONS ALONG KITCHEN COUNTER | | | SPACE. 210.52C1-5, 210.8A6 | | | BATH(S), 210.11C3,220.16. | | | PLEASE LIST AL MIN CIRCUITS REQUIRED PER | | | NEC 2002 | | | PLEASE INCLUDE PANEL SCHEDULE WITH | | | CIRCUITING ETC. | | | 106.1.2 | | | | | | 2) NOTE: PLEASE SEE 2004 R313 AND SHOW | | | ALL LOCATIONS OF NEW OR EXISTING SD'S | | | EITHER MEETING THE CURRENT NFPA-72 | | | 11.5.1.1 OR NEW TO BE INSTALLED. | | | | | | 3) NOTE: PLEASE BE SURE TO SEE 210.12B | | | FOR ARC FAULT PROTECTION. | | | | | | 4) NOTE: PLEASE SEE THAT PLANS SHALL BE | | | DONE BY AN ARCHITEC AT A MIN. FS 481.229 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|