Plan Review Notes
Plan Review Notes For Permit 06071012
Permit Number 06071012
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-27 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE PROVIDE AN ELECTRICAL
 LAYOUT FOR COMPLETE SCOPE OF ELECTRICAL
 WORK.
 PLEASE INDICATE ALL NEW OR EXISTING GFI
 RECEPT LOCATIONS ALONG KITCHEN COUNTER
 SPACE. 210.52C1-5, 210.8A6
 BATH(S), 210.11C3,220.16.
 PLEASE LIST AL MIN CIRCUITS REQUIRED PER
 NEC 2002
 PLEASE INCLUDE PANEL SCHEDULE WITH
 CIRCUITING ETC.
 106.1.2
  
 2) NOTE: PLEASE SEE 2004 R313 AND SHOW
 ALL LOCATIONS OF NEW OR EXISTING SD'S
 EITHER MEETING THE CURRENT NFPA-72
 11.5.1.1 OR NEW TO BE INSTALLED.
  
 3) NOTE: PLEASE BE SURE TO SEE 210.12B
 FOR ARC FAULT PROTECTION.
  
 4) NOTE: PLEASE SEE THAT PLANS SHALL BE
 DONE BY AN ARCHITEC AT A MIN. FS 481.229
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  