| Notes |
| Date |
Text |
| 2007-04-05 07:32:14 | 1) NOTE: PLEASE SEE ROOM/AREA WHICH SEEMS TO CONTAIN | | | PARTITIONS WHICH WOULD REQUIRE AN AUTOMATED DEVICE PER | | | 13-415.1.ABC.1.1, .1.2. | | | THESE WALLS ARE NOT CLEAR AND THIS IS TO BE VERIFIED IN | | | FIELD. | | | | | | 2) NOTE: PLEASE SEE ROOM ON PLANS WHERE PANEL IS | | | LOCATED. THIS ROOM ON PREVIOUS PLANS CONTAINED A DESK, | | | COMPUTER STATION ETC. NOW, WHAT APPEARED TO BE A SMALL | | | OFFICE AREA NOW APPEARS TO BE A CLOSET. PLEASE KNOW THE | | | ELECTRICAL PANEL MAY NOT BE IN A STORAGE CLOSET. | | | 110.26, 240.24, 408.7. | | | PLEASE SEE PLANS HAVE BEEN REDLINED FOR THIS AS OVER | | | CURRENT PROTECTION IS NOT TO BE LOCATED IN THE | | | IMMEDIATE VICINITY OF EASILY IGNITABLE MATERIALS. | | | | | | ** PLEASE REVISE THE ABOVE ALONG WITH ANY OTHER | | | REVISIONS BEFORE THE ROUGH ELECTRICAL INSPECTION. | | | | | | *IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | |
|