| 2007-02-07 14:30:31 | *** UNSAT **** |
| | |
| | |
| | 1) NOTE: PLEASE SEE NOT ALL AREAS APPEAR TO CONTAIN A |
| | DEVICE. PLEASE SEE ONE SET OF PLANS WHICH HAS THIS AREA |
| | REDLINED. |
| | PLEASE ALSO KNOW THAT THE STATE WAS CONTACTED AND |
| | PLEASE SEE THE DEFINITIONS AS STATED IN THE FBC AND |
| | EVEN IN CHAPTER 13. PLEASE SEE THE RESPONSE LETTER |
| | MENTIONS TO SEE *SEPARATE BUILDING* ETC, HOWEVER PLEASE |
| | SEE THE MINIMUM REQUIREMENTS FOR THE WALL. THE FIRE |
| | WALL DEFINITION IS PROVIDED IN CHAPTER 13. |
| | 13-415.1.1, .1.2 AND .1.3 |
| | 13-415.2, 13-415.1.AB.1 |
| | |
| | ** PLEASE KNOW THAT UPON CONSULTATION WITH ANN STANTON |
| | FROM THE STATE DEPARTMENT OF COMMUNITY AFFAIRS AND AS |
| | FOR ELECTRICAL CODE COMPLIANCE WITH THE LIGHTING |
| | PERFORMANCE AND ENERGY CALCULATIONS COME UP TO THE |
| | FIGURES AS SET FORTH THEN PLEASE CALL TO GO OVER HOW |
| | THIS CAN POSSIBLY BE SHOWN IN COMPLIANCE ON PLANS. |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS HAVE NOW COME BACK WITH A |
| | COMPLETELY NEW *SIGNATURE* FROM THE DESIGN |
| | PROFESSIONAL. PLEASE SEE THAT THE PLANS NOW APPEAR TO |
| | SHOW SOME KIND OF INITIALS INSTEAD WHICH DO NOT |
| | CORRELATE WITH THE ORIGINAL SIGNATURE OF RECORD IN ANY |
| | WAY. |
| | PLEASE SUPPLY AND SUBMIT A SIGNED, DATED, SEALED AND |
| | NOTARIZED LETTER ATTESTING TO THE LEGAL SIGNATURE OF |
| | THE DESIGNER OF RECORD. |
| | FS 481.221. |
| | PLEASE KNOW THAT IN NO CASE MAY ANY OTHER PERSON THAN |
| | THE LICENSE HOLDER SIGN PLANS.PLEASE KNOW THAT AT |
| | THIS TIME EACH SET OF PLANS ARE BEING RETAINED BY THIS |
| | OFFICE. |
| | PLEASE BE SURE THE NOTARIZED LETTER IS PROPERLY |
| | NOTARIZED PER FS 117.05 |
| | |
| | *PLEASE ALSO SEE THAT THE SEAL IS REQUIRED TO BE CLEAR |
| | AND VISIBLE WITH ALL INFORMATION ON SAID SEAL. PLEASE |
| | SEE FS 481.221 AND FAC 61G1-16.003 |
| | MANY OF THE SEALS ARE VERY FAINT AT THIS TIME AND NOT |
| | EASILY READABLE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |